Appendix
■
Glossar
Changes during operation
"Yes" means that the parameter can be changed,
while the VLT frequency converter is in operation.
"No" means that the VLT frequency converter must
be stopped before a change can be made.
4-Setup
"Yes" means that the parameter can be program-
med individually in each of the four setups, i.e. the
same parameter can have four different data
values.
"No" means that the data value will be the same in
all four setups.
Conversion index
This number refers to a conversion figure to be
used when writing or reading by means of a VLT
frequency converter.
Conversion index Conversion factor
74
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
Data type
The data type shows the type and length of the
telegram.
Data type
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string