MG.90.D1.02 – VLT is a registered Danfoss trademark
28
VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
■
GSD file
The GSD file is a “standard” DP text file which
contains the necessary data for the configuration
of DP slaves within a standard DP master.
#Profibus_DP
Vendor_Name = „DANFOSS A/S“;
Model_name = „VLT® 5000/6000“;
Revision = „01“;
Ident_Number = 0x0402;
Protocol_Ident = 0;
Station_type = 0;
FMS_supp = 0;
Hardware_Release = „4.0“;
Software_Release = „2.04“;
9.6_supp = 1;
19.2_supp = 1;
93.75_supp = 1;
187.5_supp = 1;
500_supp = 1;
1.5M_supp = 1;
3M_supp = 1;
6M_supp = 1;
12M_supp = 1;
MaxTsdr_9.6 = 60;
MaxTsdr_19.2 = 60;
MaxTsdr_93.75 = 60;
MaxTsdr_187.5 = 60;
MaxTsdr_500 = 100;
MaxTsdr_1.5M = 150;
MaxTsdr_3M = 250;
MaxTsdr_6M = 450;
MaxTsdr_12M = 800;
Redundancy = 0;
Repeater_Ctr_Sig =0;
24V_Pins = 0;
Freeze_Mode_supp = 1;
Sync_Mode_supp = 1;
Auto_Baud_supp = 1;
Set_Slave_add_supp = 0;
Usr_Prm_Data_Len = 0;
Min_Slave_Intervall = 06;
Modular_Station = 1;
Max_Module = 2;
Max_Input_Len = 28;
Max_Output_Len = 28;
Max_Data_Len = 56;
Max_Diag_Data_Len = 8;
Unit_Diag_Bit(1) = „Overflow SPM-FIFO“;
Unit_Diag_Bit(2) = „Actual value is not updated“;
Module = „PPO 1 Module consistent PCD“ 0xF3, 0xF1;
EndModule;
Module = „PPO 1 Word consistent PCD „ 0xF3, 0x71;
EndModule;
Module = „PPO 2 Module consistent PCD“ 0xF3, 0xF5;
EndModule;
Module = „PPO 2 Word consistent PCD „ 0xF3, 0x75;
EndModule;
Module = „PPO 3 Module consistent PCD“ 0xF1;
EndModule;
Module = „PPO 3 Word consistent PCD „ 0x71;
EndModule;
Module = „PPO 4 Module consistent PCD“ 0xF5;
EndModule;
Module = „PPO 4 Word consistent PCD „ 0x75;
EndModule;
Module = „PPO 5 Module consistent PCD“ 0xF3, 0xF9;
EndModule;
Module = „PPO 5 Word consistent PCD „ 0xF3, 0x79;
EndModule;
The required GSD file is available on the
internet at
http://www.danfoss-sc.de.
In the configuration of the PPO types (informative
data telegrams), a distinction is made between
module consistency and word consistency:
Module consistency means that a particular portion
of the PPO is defined as a connected module.
The parameter interface (PCV, length 8 byte) of the
PPO always has module consistency.
Word consistency means that a particular portion
of the PPO is divided into individual data sectors
of word size (16 bit).
The process data (PCD) of the PPO can have either
module consistency or word consistency, as de-
sired.
Some PLCs, such as the Siemens S7, require spe-
cial functions to address modules that are longer
than 4 byte (in the case of Siemens: ”SFC”, see
Master Manual).
This means that, in the case of Siemens (S7), the
PCV interface of the PPOs can only be addressed
through the SFC functions.
GSD file