MG.90.D1.02 – VLT is a registered Danfoss trademark
36
VLT
®
5000/5000 Flux/6000 HVAC/8000 AQUA PROFIBUS
Description of the selection
– Not active:
The function is not active.
– Save operations setup:
All parameter setups of
the active setup are saved in EEPROM. The
value returns to
Not active
after all parameter
values have been saved.
– Save program setup:
All parameter setups of the
setup being processed are saved in EEPROM.
The value returns to
Not active
after all parame-
ter values have been saved.
– Save all setups:
All parameter setups in all
setups are saved in EEPROM. The value returns
to
Not active
after all parameter values have
been saved.
980-982 Defined parameters
(DEFINED PARAM.)
Value
Read only
Function
The three parameters contain a list of all parame-
ters defined in the VLT. Every one of the three
parameters can be read as an array with subindex
255 with the help of the acyclical FMS-
Read s
er-
vice. When the corresponding subindex is used,
individual elements from the list can also be read
by means of DP and cyclical/acyclical FMS. The
subindices begin with 1 and follow the sequence
of the parameter numbers.
Each parameter contains up to 116 elements (pa-
rameter numbers). The number of parameters that
are in use (980, 981 and 982) depends on the re-
spective VLT configuration.
When a 0 is issued as a parameter number, the list
ends.
990-992 Modified parameters
(MODIFI. PARAM.)
Value
Read only
Function
The three parameters contain a list of all parame-
ters that have been changed from the factory set-
ting. Every one of the three parameters can be
read as an array with the help of the acyclical
FMS-
Read s
ervice. When the corresponding subin-
dex is used, individual elements from the list can
also be read by means of DP and cyclical/acycli-
cal FMS. The subindices begin with 1 and follow
the sequence of the parameter numbers. Each
parameter contains up to 116 elements (parameter
numbers). The number of parameters that are in
use (990, 991 and 992) depends on how many pa-
rameters have been modified in comparison with
the factory setting.
Pure read parameters (Read only), such as data
output parameters, are not logged as modified
even if they are changing.
When a 0 is issued as a parameter number, the list
ends.
Parameters