Operating Instructions
BD Controller 101N07xx Series 24 V DC
16
DEHC.PS.100.I.02
4.2.3 Compressor
The speed and thereby the capacity of the compressor is set using the
Requested speed
parameter.
During start up, the compressor can be run at a lower speed,
Start speed
, than Requested speed.
The duration of the period running at
Start speed
is set using the
Start time
parameter.
The compressor is protected against operation below minimum speed. Lubrication of the compressor
will be very poor at excessively low speed and therefore low speed operation can lead to destruction
of the compressor. Speed limits are: min 1850 rpm; max speed 4300 rpm.
If the compressor speed falls below the minimum or exceeds the maximum speed, the compressor will
stop and an alarm
Min speed failure or Max. speed failure
will be sent. The compressor will try to restart
after the set
Restart time
. The
Restart time
default is 60 sec.
The fans will continue to run.
Name
Default
Max value
Min value
Step
Unit
Requested speed
4000
4000
2500
100
rpm
Start delay
4
240
2
1
Seconds
Start speed
2500
4000
2500
100
rpm
Start time
30
600
0
1
Seconds
Settings
Measurements
Name
Description
Step
Unit
Compressor speed
Real-time compressor speed(+/-10%)
1
rpm
Measurements
Name
Description
Step
Unit
Cut-in level
Calculated value. Cutin = Diff.
0.1
Volt
Supply voltage
Real-time - voltage measured on + & - terminals
0.1
Volt
Содержание 101N0715
Страница 2: ...Operating Instructions BD Controller 101N07xx Series 24 V DC 2 DEHC PS 100 I 02...
Страница 4: ...4...
Страница 6: ...6...
Страница 10: ...10...
Страница 12: ...12...
Страница 23: ...Operating Instructions BD Controller 101N07xx Series 24 V DC 23 DEHC PS 100 I1 02...
Страница 24: ...24...
Страница 26: ...26...