4.2 Description of
Parameters
4.2.1 Main Functions
In order to start and stop the compressor the Main Switch can be set to ON or OFF .
OEMs making an interface with custom design electronics via Modbus must be able to control the
CCU ON / OFF via the Main Switch.
ON: All functions are active.
OFF: All main functions are inactive, however
• Battery monitoring active
• NTC temperature sensor monitoring active
• Auxiliary temperature sensor monitoring active
• PCB inverter temperature monitoring active
4.2.2 Battery protection
The battery protection serves to avoid permanent damage to the battery by discharge.
The setting range is from 19 to 27 V DC.
Critical stop without delay if voltage drops below 17 V DC or exceeds 31.5 V DC
Tolerances are ± 0.30 V DC
31.5 V DC
Name
Default
Max value
Min value
Step
Unit
Main switch
OFF
ON
OFF
1
-
Settings:
Settings
Name
Default
Max value
Min value
Step
Unit
Battery cutout level
21.3
27
19
0.1
Volt
Battery cutin diff.
3.9
10
0.5
0.1
Volt
Cutout delay
3
60
0
1
Seconds