060L2110

DKRCC.PI.CA0.F2.22 | 2

Wiring

Note

Caution

Important

Do not dent or deform the bulb of the 

thermostat, as doing so could damage 

the bulb and cause charge

leakage.

Do not turn any other screws except 

screws on the scale plate, on the micro 

switch knob and on the terminal block.

Installation

Select an accessible location, where 

the thermostat will not be subject 

to damage. Mount the KPU 19 on a 

bracket or on a completely flat surface. 

Mounting on an uneven surface may 

cause incorrect thermostat operation. 

Use only the mounting holes provided 

at the back of the metal housing.

The KPU 19 thermostat and the

sensing bulb can be mounted in any 

position.

The sensing element is filled in with

liquid expansion type charging with

no limitations in terms of temperature 

at switch body (TS), temperature at 

sensing bulb (TB) or temperature at 

capillary tube (TC). KPU 19 can operate 

in all following conditions:

TS > TB; TS < TB, TS = TB.

Taking into consideration time 

constant of the thermostat it is 

recommended to install KPU 19 where 

temperature is not changing rapidly.

Fast changes of the measured 

temperature will cause thermostat 

measurements lags behind actual 

temperature changes in the 

application. Make sure to keep

temperature variable acceleration

within 3 minutes per 1.8 °F at liquid, or 

within 18 minutes per 1.8 °F at air. KPU 

should be installed in a place in which 

harmful environmental conditions like 

radiation from sun, lamps or radiator is 

minimalized.

Cooling due to the extensive air flow 

might affect thermostat performance 

as well.

It is recommended to install the

thermostat at a place where vibration 

is 1G or less.

Do not make additional holes.

Locking mounting holes must be

fastened at position A as shown in

diagram to the right.

Fastening at position “B” may result 

in housing deformation and KPU 19 

malfunction.

                        Voltage [V]

Amps [A]

P.F. 

cos Ø

A C

120

240

Resistive load

1

0.5 ~ 16 0.5 ~ 8

Inductive 

load

Full load 

Amps

0.75 0.5 ~ 16 0.5 ~ 8

Locked 

rotor Amps

0.45

96

48

Do not remove cover while power 
is supplied as it may cause electrical 
shock.
To avoid the possibility of electric 
shock and damage to equipment, 
disconnect the power supply before 
any wiring connections are made. 
Never touch current conducting (LIVE) 
parts with your fingers or with tools.

Electrical wires should be connected 
through the conduit rubber or 
alternatively by conduit boss.

All wiring should conform to the 
National Electrical Code and to 
applicable local regulations. 
Use only copper wire. 
Use only the terminal screws furnished 
in the terminal block. 
Do not exceed tightening torque of
10 lb. in. (1.18 Nm). 
Do not exceed the thermostat’s 
specified electrical ratings.

Do not use impact driver(shock driver).
The terminal block as well as 
grounding screw are accessible after 
removing the front cover.

General recommendations for 

capillary tube and bulb installation:

1. Protect the capillary tube from 
damage due to vibration.
  a) When the thermostat unit is 
  mounted directly on the compressor, 
  the capillary tube must be secured to 
  the compressor so that both vibrate 
  together.
  b) For mounting otherwise, form 
  surplus capillary tube into a loose 
  loop and secure the loop to the base 
  on which the thermostat is mounted.

2. Leave a little slack in the capillary 
tube to help dampen vibration.

3. Avoid sharp bends (with the radius 
of 

1

/

2

" or less) and bending the capillary 

tube at the same point several times, 
as these actions can weaken the 
material and increase the likelihood of 
the tube cracking.

4. Bending of the capillary tube within 
1.75" from soldering point with bulb is 
not allowed.

5. Form and locate the capillary tube 
away from sharp or abrasive objects 
that might damage it.

6. For thermostats with room sensor 
coils, make sure that placement allows 
free airflow around the coil and bulb. 
At the same time, ensure that the bulb 
is not exposed to drafts from doors, or 
to heat radiated from the evaporator 
surface. Make sure that the bulb does 
not come into contact with a wall 
surface. Never mount the thermostat 
directly on a cold wall. Instead, mount 
the unit on an insulating plate.

7. KPU 19 sensing bulb is made of 
copper, copper alloy, silver solder – do 
not use it for media which are harmful 
for these materials.

Pilot duty: 125 VA; 120/240 V AC