06
0R
97
71
06
0R
97
71
© Danfoss | DCS (az) | 2018.10
4
3
2
5
6
M I N
Scale Plate
Cover
Mounting Hole
Capillary Tube
Conduit Rubber
Grounding Screw
Terminal Screw
DIFF.
Diff. Adjusting
Knob
1.7
0.63
0.59
0.14
0.27
4.48
2.4
0.19
0.55
2.12
Danf
oss
060L2101
0.88
remote bulb
air coil/room sensor
Danf
oss
060L2107
remote bulb
air coil/room sensor
Danf
oss
060L2107
Installation Guide
Thermostat
Type KPU 19
DKRCC.PI.CA0.F2.22 | 1
Application
KPU 19 thermostats are used for
temperature regulation in refrigeration,
freezing, air conditioning, ventilating
and heating systems.
KPU 19 thermostats are fitted with
Single-Pole Double-Throw (SPDT)
or Single-Pole Single-Throw (SPST)
contact system.
The standard KPU 19 enclosure is rated
NEMA ~ 1.
NEMA ~ 1 is obtained when the
thermostat is mounted on a flat surface
with all unused holes covered.
Remote bulb
Air coil/room sensor
Thermostat bulb types
Type
Regulating
range
Differential
Bulb size
Capillary
tube length
Max. bulb
temperature
Ambient
temperature
Contact
type
Reset
type
Code no.
[°F]
∆T [°F]
[in.]
[in.]
[°F]
[°F]
KPU 19
-30
–
80
3.6
–
12.6
3
/
8
x 4
1
/
2
120
140
-31
–
140
SPDT
Auto.
060L2150
KPU 19
-30
–
80
3.6
–
12.6
3
/
8
x 4
1
/
2
80
140
-31
–
140
SPST (close
on temp. rise)
Auto.
060L2151
KPU 19
-30
–
80
3.6
–
12.6
-
Air coil /
Room sensor
140
-31
–
140
SPDT
Auto.
060L2152
Product specification
Dimensions [in.]
Important
The KPU 19 thermostat is designed
only for use as a temperature
regulating operating control. It is
the responsibility of the installer
to verify that other necessary
safety controls are installed and
functioning properly as intended
by the original equipment
manufacturer or system design.