212-0024-SS
9
July 30th, 2019
Programming the PDU-16SS
NOTE: If no action is taken within 20 seconds during setup, the PDU will return to Standby Mode.
Low Voltage Shutdown Setup
The PDU-16SS’ factory default LOW VOLTAGE SHUTDOWN value is set to 11.5 VDC for both Group 1 and
Group 2 outputs. This value can be adjusted by the user for each of the two output groups separately by fol-
lowing these steps:
Tap the VOLTAGE SETUP/RESET button. The VL GRP1 LED will turn ON and the display will show the
current voltage set for GROUP 1 outputs. Tap the UP or DOWN buttons to enter the new voltage.
Tap the VOLTAGE SETUP/RESET button. The VL GRP2 LED will turn ON and the display will show the
current voltage set for GROUP 2 outputs. Tap the UP or DOWN buttons to enter the new voltage.
Tap the VOLTAGE SETUP/RESET button again to save the new values.
Note: - When the vehicle battery voltage drops below the Low Voltage Shutdown values for GROUP 1
or GROUP 2 outputs, the outputs for that group will be OFF unconditionally.
- The
minimum shutdown voltage cannot be set below 11.5VDC unless the vehicle is being fitted
with a second battery.
Timed Shutdown Setup
The PDU-16SS factory default shutdown times are set to:
2 minutes for GROUP 1 outputs
2 hours for GROUP 2 outputs
This value can be adjusted by the user for each of the two output groups separately by following these steps:
Tap the TIME SETUP/TEST button. The TIME GRP1 LED will turn ON and the display will show the cur-
rent shutdown time set for GROUP 1 outputs. Tap the UP or DOWN buttons to enter the new time de-
lay.
Tap the TIME SETUP/TEST button. The TIME GRP2 LED will turn ON and the display will show the cur-
rent shutdown time set for GROUP 2 outputs. Tap the UP or DOWN buttons to enter the new time de-
lay.
Tap the TIMER SETUP/TEST button again to save the new values.
Note:
When the vehicle IGNITION switch is turned on, the countdown will be stopped.