Dryair DK200 - Dryair DK220
A01
: Control circuit transformer
A30
: Compressor chankaser heater
B15
: Control circuit supply
EMR4
: Phase protection relay
F1,F2
:
A01 Primary protection
F3, F4:
A30 overload protection
M1
: Compressor motor
M10
: Fan motor 1
M1
1
: Fan motor 2
P1
: Overload protector of compressor
P10
: Overload protector of fan motor
Q1
: Compressor contactor
Q10
: Fan contactor
X1
: Main supply connection
terminal block
ELECTRICAL
SPECIFICA
TIONS
COMPRESSOR
UN 400V/3/50
F
AN MOT
OR
UN 400V/3/50
Dryair DK 200 FLA
28
A
5.63
Kw
Dryair DK 210 FLA
34
A
6.79
Kw
Dryair DK 220 FLA
41
A
9 Kw
Dryair DK 200 FLA
2.63
A
0.780
Kw
Dryair DK 210 FLA
2.63
A
0.780
Kw
Dryair DK 220 FLA
2.63
A
0.780
Kw
SIZE IS
AMPS-600 V
AC
ELECTRICAL
SUPPL
Y
LINE
3 PHASE + PROTECTION EARTH
CABLE SIZE
Dryair DK200
Dryair DK210
Dryair DK220
4G10mm
4G16mm
4G16mm
MAXIMUM SET : 15%
FIELD INST
ALLED
MAIN PROTECTION
AND DISCONNECTING MEANS SHALL
BE PROVIDED BY
THE INST
ALLER OF RESIDUAL
CURRENT
AUT
OMA
TIC CIRCUIT BREAKER
17