DAKTRONICS AQUATICS MAINTENANCE CHECKLIST 

 

DD3691471  072017 

201 Daktronics Drive  PO Box 5128  Brookings, SD 57006-5128 

 

800-325-8766  605-692-0200  fax 605-697-4700 

www.daktronics.com  email [email protected] 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diving Judge 

Controls 

 

 

 

 

 

 

 

 

Using standard Ethernet cable, connect from Hy-Tek computer to the 

ETHERNET jack on the back of the OmniSport. 

 

MENU > 4 > 7 > 7 NETWORK MMR: ON 

 

Ensure that the IP address is within range of the OmniSport IP, and 

the Subnet and Gateway match. 

o

 

Open Hy-Tek software to configure settings. Start by entering the Run screen 

from the top header. 

 

Interfaces > Setup > Timing Console Interface > Daktronics 

OmniSport 2000 (Serial or UDP). 

 

Interfaces > Setup > Scoreboard > Daktronics (Serial or UDP). 

***Alpha Scoreboard Interface needed for matrix RTD.

 

o

 

Some setups use Generic Serial for Alternative 

configurations (CTS Timer). 

 

 

o

 

Verify judge console firmware is up to date (3.0 or higher). JC-100 and  

RC-100 options. 

o

 

Verify base station firmware is up to date if using wireless judge consoles  

(3.0 or higher). 

o

 

Verify the base station function. Function setting should be set to a 6 on 

version 3.0 and higher. (Function 1 for earlier versions). 

o

 

Verify the correct 900 MHz antenna is being used on the base station. 

o

 

Verify the judge consoles are communicating to the OmniSport 2000.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detailed Instructions: ED-13312 (Section 7)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pace Clocks 

 

 

 

 

 

 

 

 

 

 

 

o

 

Visually inspect space clock (switches, knobs, and connections). 

o

 

Verify pace clock firmware is up to date. 

o

 

Verify pace clock operation. 

 

 

After completing the checklist:  

    Still having issues? 

o

 

Search ou

Knowledge Base

 for additional  

troubleshooting resources.

 

o

 

Create a new service case in your 

MySupport Account

 

PC-2001 Manual: ED-13737

 

PC-2002 Manual: ED-14253 

TI-2022 Manual: ED-13736 

 

Содержание Aquatics

Страница 1: ... o Verify that thermal paper is installed in printer location and feeds prints correctly o Power up OmniSport console to verify firmware is up to date update if needed Must be newer than 8 3 27 to update in the field o Perform Mock swim race after completing checklist to verify all inputs and outputs are working including scoreboard RTD data OmniSport 2000 Manual ED 13312 On deck Equipment lane mo...

Страница 2: ...hes knobs cabling and connections o Testing 1 Test for charger functionality by connecting to the HS 200 Charging LED should light when plugged in 2 Ensure microphone is connected to the horn start assembly Wireless models ensure belt pack has a new battery and matches the wireless channel set on the HS 200 base assembly and has the antenna mounted on the base unit 3 Set volume controls to desired...

Страница 3: ...and when pressing on the pad it should create a shorted connection 4 If the pad passes the try test it can be put in the water to complete the we test by measuring for DC voltage Wet Test 1 1 Place all touchpads into the water and connect to their lane connections 2 Turn on the OmniSport 2000 and go into swimming mode 3 Press MENU 5 2 and go into the test mode 4 Use your hand or a swimmer to tap t...

Страница 4: ...nto the lane harness and the OmniSport connected and setup in Swimming mode 3 Place your hand flat on the RTOP and hold for two seconds 4 Remove you hand quickly and the red LED will turn solid for 1 second then return back to a flashing ready state 5 The RTOP time should also be able to be captured on the OmniSport printout as long as settings event are configured correctly Relay Take off Platfor...

Страница 5: ...al cable adapter on the Pro Dive computer o Verify communication between devices May need to change com port value in Pro Dive or set to UDP o Tip When using serial connections with an Ethernet OmniSport the network port must be disabled to allow serial communications MENU 4 7 7 NETWORK PRO OFF will allow you to shut off the Network Pro option Detailed Instructions ED 16444 Hy Tek Meet Manager o V...

Страница 6: ...setups use Generic Serial for Alternative configurations CTS Timer o Verify judge console firmware is up to date 3 0 or higher JC 100 and RC 100 options o Verify base station firmware is up to date if using wireless judge consoles 3 0 or higher o Verify the base station function Function setting should be set to a 6 on version 3 0 and higher Function 1 for earlier versions o Verify the correct 900...

Отзывы: