SOFTWARE
CONNECTION NIKI 1100/1500 Plus
The UPS is equipped with a RS232 interface (DB9 cable for software
communication is needed) and USB interface, thanks to which it is possible
by means of a computer to access a set of data regarding the operation of
the UPS and control the operating system unattended shutdown.
Software is available as on option for Win98/ME/2000, Novell and Linux,
from the website www.daker.com without charge.
User license is included in the product.
TELEPHONE PROTECTION
The NIKY UPS has an integrated, standard RJ11/RJ45 passing telephone
connectionthat provides protection for telephone or network equipment
(modem, telephones, etc.) against overvoltage.
CHANGING BATTERIES
CAUTION
Opening, repairing, or replacing parts inside the UPS must always be carried
out by specialized technical personnel only.
First of all, switch off the UPS with the ON/OFF button located on the front
panel, then unplug the power cable from the 230V outlet socket.
1) Switch off the uninterruptible power supply.
2) Unplug the power cable from the mains socket.
3) Change the batteries with others of the same type and make, or having
the same features
Keep clear from fire to avoid explosion while handling batteries.
Do not open or tamper with the battery case, because it contains toxic
electrolyte that could be harmful for your skin or eyes. Keep out of children’s
reach.
NOTICE
The batteries must only be replaced by qualified technical personnel, who will
dispose of them in compliance with the law in force.
POSSIBLE MALFUNCTIONING
The UPS always operates on batteries:
•
There is no line voltage
•
Line voltage is out of allowed UPS range
•
The power supply cable is not correctly connected to mains socket.
•
The input circuit breaker has to be reset
•
The mains socket is defective
The UPS signals overloading:
•
Additional loads to the ones normally connected have involuntarily been
connected on the output line.
•
Check all the loads connected to the output
The UPS doesn’t operate in battery mode (it shuts down or immediately
signals it is close to the operating limit):
•
The UPS has operated with no mains voltage for a long time and has not
been able to recharge the battery. Recharge it for at least 6 hours by
connecting the uninterruptible power supply to the mains.
•
The battery is flat due to not using the UPS for a long period. Recharge it
for at least 6 hours by connecting the uninterruptible power supply to the
mains.
•
The battery has run down due to being used frequently, to ambient
conditions, or to having exceeded its average service life; it is necessary
to change it.
The UPS doesn’t deliver power to the output:
•
Check that the loads are correctly connected to the output sockets
TECHNICAL FEATURES
Construction Specifications
Weights
Dimensions L x H x P in mm
Protection
Ambient specifications
Operating temperature range
Operating relative humidity range
Degree of protection as per IEC529
Noise level at 1 meter
< 40 dBA
Electrical input specifications
Rated input voltage
230 V
Range of input voltage
1 7 5 - 2 8 5 VAC
Rated input frequency
50 or 60 Hz ± 1 Hz
Maximum input current
Number of input phases
Single phase
Waveform on output
With battery operation
Type of operation
Electrical specifications on output
Rated output voltage
Output current on nominal load
Active output power on nominal load
Apparent output power on nominal load
Overload capacity
110% for 5 s.
Number of phases on output
1100
13 Kg.
6,2 Arms
4,7 Arms
600 W
1100 VA
1500 VA
900 W
6,5 Arms
8,5 Arms
from 0 to +40 °C
from 0 to 90% non-condensing
step wave
line interactive
Single phase
IP20
147 X 234 X 360
Electronic protection against overloading and short-circuiting
Shutdown on reaching operating limit and overheating.
Automatic shutdown due to protection triggering
16 Kg.
1500 Plus
MetaSystem reserves to itself the right to modify the above specified data
without previous notice.
©Copyright by MetaSystem SpA
The batteries are considered hazardous waste and should be disposed of
in accordance with current regulations.
Electrical specifications on output with battery operation
Rated output voltage
230 V ± 10%
Output frequency
Active output power on non-linear load
Apparent output power on non-linear load
Battery operation
Operating time (with batteries charged)
with an two PC load + 15” monitor
Charging time
Technical data and number of batteries
Standards
Electromagnetic compatibility
Emission - Immunity
Safety
Performance and features
n°2 maintenance-free,
sealed, lead-acid battery
12V 9 Ah
50/60 Hz ± 1Hz
10/12 h at the end of operating range
Conforms to EN 50091 - 2
Conforms to EN 62040 -1 -1
Conforms to EN 62040 - 3
600 W
900 W
1100 VA
20 min.
n° 2 maintenance-
free, sealed, lead-
acid batteries 12V
7,2 Ah
25 min.
1500 VA
115/230 V ± 15 %