6. Keypad lock: Press
for 5 seconds to
display will be shown. Keypad lock function is working. Under
this function, any keypad is locked. Press
for 5 seconds to
display will disappear, keypad lock function
is not working.
7. Timer ON: With thermostat OFF, press
for 5 seconds to Timer ON setting. The setting time range is from 30 to 720
minutes. Press Up button once to increase 30 min. Press Down button to reduce 30 min once.
8. Timer OFF: With thermostat ON, press
for 5 seconds to Timer OFF setting. The setting time range is from 30 to
720 minutes. Press Up button once to increase 30 min. Press Down button to reduce 30 min once.
Sleep mode: With thermostat ON, press
for 5 seconds to
display to activate, sleep mode is working.
Parameters setting
With thermostat OFF, press
+
for 5s to parameters setting mode. Press
once, LED number is changed
from 1 to 20. The number represents 20 parameters.
No1 stands for unit type setting:
0=Air cleaner, Mode Icon only show “Fan”. Temperature,
RH, CO2, PM2.5, VOCs are shown on LED.
1=AHU unit, Mode Icon show “Cooling, heating, ventilation, dehumidifier, Auto”. Only temperature show on LED.
2=Full function unit (AHU+ Air quality). Mode Icon show “Cooling, heating, ventilation, dehumidifier, Auto”. Only temperature
,
RH, CO2, PM2.5, VOCs are shown on LED.
3=Fan coil thermostat. M
ode Icon show “Cooling, heating, ventilation”. Only temperature show on LED.
No2 stands for temperature unit setting:
0=degree C
1=degree F
No3 stands for temperature display setting:
0=Room temperature display on LED
1=Setting temperature display on LED
No4 stands for setting temperature range setting:
0=setting temperature range is from 16~30
1=Setting temperature range is fixed. Cooling=24°C, Heating=21°C
No5 stands for temperature band setting: 1~9, default: 1
No6 stands for PM2.5 setting: 30~200, default: 60
No7 stands for PM2.5 band setting: 10~80, default: 50
No8 stands for CO2 setting: 460~1200, default: 800