Swimming pool heat pump
- 21 -
MAINTENANCE & TROUBLESHOOTING
Maintenance
●
●
●
●
Check water supply device and drainage often. Make sure avoid the condition of no water or
air entering into system, as this will influence unit’s performance and reliability. Clear the pool/spa
filter regularly to avoid damage to the unit as a result of the dirty of clogged filter.
●
●
●
●
The area around the unit should be dry, clean and well ventilated. Clean the sides heating
exchanger regularly to maintain good heat exchange as conserve energy.
●
●
●
●
The operation of the refrigerant system should only be serviced by a certified technician.
●
●
●
●
Check the power supply, cable connection and water system regularly.
●
●
●
●
When the ambient temperature lowers to less than 2
℃
the heat pump must be switched on,
to avoid freezing. If the machine is switched off or there is electric power outage, discharge all
water in the water pump and water system, so that freezing of the water in the pump or water
system does not occur. Discharge the water at the bottom of water pump, if the unit will not be
used for an extended period of time. Check the unit thoroughly and fill the system with water fully
before using it for the first time after a prolonged period of no usage.
Trouble shouting guide
Failure code and removal for the smart PCB
If a malfunction can not be resolved immediately, in order to analyze the problem, we will need to
know the message (error code) that is displayed on the controller. The follow is an overwies of
different ERROR code, along with directions to solve them.
Code
Fault
Check
Solution
PP 01 or
PP 1
Return
water
temperature
sensor failure
1.
Check the connection of the return
water temp.sensor.
2.
Check whether the sensor is broken.
1.
Reconnect the sensor.
2.
Replace the sensor.
PP 02 or
PP 2
Outlet
water
temp.
sensor
failure
1.
Check the connection of outlet
water temp. Sensor.
2.
Check if the sensor is broken.
1.
Reconnect the sensor.
2.
Replace the sensor
with a new one.
PP 03 or
PP 3
Coil
temp.
sensor failure
1.
Check the connection of the coil
temp.sensor.
2.
Check whether the sensor is broken.
1.
Reconnect the sensor.
2.
Replace the sensor.
Содержание DSP?45HCA
Страница 8: ...Swimming pool heat pump 7 Vertical models DSP 180HCA DSP 180HCA 3 DSP 230HCA DSP 230HCA 3 DSP 260HCA 3...
Страница 13: ...Swimming pool heat pump 12 Project Installation sketch map...
Страница 15: ...Swimming pool heat pump 14 Circuit diagram Model DSP 45HCA DSP 65HCA DSP 85HCA DSP 100HCA DSP 120HCA...
Страница 16: ...Swimming pool heat pump 15 Model DSP 180HCA 3 DSP 230HCA 3 DSP 260HCA 3...