Swimming pool heat pump 

 

- 21 - 

 
MAINTENANCE & TROUBLESHOOTING 
 

Maintenance 

●  

 

 

 

Check water supply device and drainage often. Make sure avoid the condition of no water or 

air entering into system, as this will influence unit’s performance and reliability. Clear the pool/spa 

filter regularly to avoid damage to the unit as a result of the dirty of clogged filter. 

●  

 

 

 

The  area  around  the  unit  should  be  dry,  clean  and  well  ventilated.  Clean  the  sides  heating 

exchanger regularly to maintain good heat exchange as conserve energy. 

●  

 

 

 

The operation of the refrigerant system should only be serviced by a certified technician. 

●  

 

 

 

Check the power supply, cable connection and water system regularly. 

●  

 

 

 

When the ambient temperature lowers to less than 2

  the heat pump must be switched on, 

to  avoid  freezing.  If  the  machine  is  switched  off  or  there  is  electric  power  outage,  discharge  all 

water  in  the  water  pump  and  water  system,  so  that  freezing  of  the  water  in  the  pump  or  water 

system  does not  occur. Discharge  the  water  at the bottom  of  water  pump,  if the  unit  will  not be 

used for an extended period of time. Check the unit thoroughly and fill the system with water fully 

before using it for the first time after a prolonged period of no usage. 

 
 

Trouble shouting guide 

Failure code and removal for the smart PCB 

If a malfunction can not be resolved immediately, in order to analyze the problem, we will need to 

know  the  message  (error  code)  that  is  displayed  on  the  controller.  The  follow  is  an  overwies  of 

different ERROR code, along with directions to solve them. 

Code 

Fault 

Check 

Solution   

PP 01 or 

PP 1 

Return 

water 

temperature 
sensor failure 

1.

 

Check  the  connection  of  the  return 
water temp.sensor. 

2.

 

Check whether the sensor is broken. 

1.

 

Reconnect the sensor. 

2.

 

Replace the sensor. 

PP 02 or 

PP 2 

Outlet 

water 

temp. 

sensor 

failure 

1.

 

Check  the  connection  of  outlet 
water temp. Sensor. 

2.

 

Check if the sensor is broken. 

1.

 

Reconnect the sensor. 

2.

 

Replace  the  sensor 
with a new one. 

PP 03 or 

PP 3 

Coil 

temp. 

sensor failure 

1.

 

Check  the  connection  of  the  coil 
temp.sensor. 

2.

 

Check whether the sensor is broken. 

1.

 

Reconnect the sensor. 

2.

 

Replace the sensor. 

 
 

Содержание DSP?45HCA

Страница 1: ...Air Source Swimming Pool Heat Pump USER MANUAL DSP 45HCA DSP 65HCA DSP 85HCA DSP 100HCA DSP 120HCA DSP 180HCA DSP 180HCA 3 DSP 230HCA DSP 230HCA 3 DSP 260HCA 3...

Страница 2: ...p when running It may touch the fan and damage it or lead to accidents especially for the children Do not use the unit without the grid in case it may lead to any accidents 6 For safety reasons please...

Страница 3: ...Swimming pool heat pump 2 Content Product brief instruction 3 Technical data 4 Unit dimension 6 Installation 8 Electric connection 13 Controller operation instruction 16 Maintenance Troubleshooting 22...

Страница 4: ...l water Your existing water pump circulates the water through the heat pumps heater usually next to the pool equipment and the water warms up This pool heat pump is also of cooling function User can c...

Страница 5: ...220 240 1 50 Setting Temp Range 15 45 Running Temp Range 5 43 Water Inlet Outlet Dimension 50 8mm Water Heat Exchanger Titanium Water Flow m3 h 3 4 4 4 5 4 5 Refrigerant R410A Unit Dimension W H D mm...

Страница 6: ...Temp Range 5 43 Water Inlet Outlet Dimension 50 8mm Water Heat Exchanger Titanium Water Flow m3 h 7 5 8 5 Refrigerant R410A Unit Dimension W H D mm 820X720X1055 Net Weight KG 119 119 133 133 148 Disp...

Страница 7: ...ol heat pump 6 UNIT DIMENSIONS Horizontal models Model A mm B mm C mm D mm E mm DSP 45 HCA 510 306 266 276 410 DSP 65 85 HCA 552 995 284 344 680 DSP 100 HCA 617 1118 350 290 660 DSP 120 HCA 650 1140 4...

Страница 8: ...Swimming pool heat pump 7 Vertical models DSP 180HCA DSP 180HCA 3 DSP 230HCA DSP 230HCA 3 DSP 260HCA 3...

Страница 9: ...installed on the floor its undercarriage should be heightened to avoid ingression of accumulated water in rainy season In snowy areas it is important to prevent accumulated snow from blocking up the a...

Страница 10: ...led anywhere outdoors providing minimum distance requirements are met with respect to other objects For indoor pools please consult your installer Attention Do not place the unit in an enclosed area w...

Страница 11: ...hould be avoided as much as possible as machine falling down may result in severe accident Distance from the pool Normally the pool heat pump is installed within a 7 5 meter radius of the swimming poo...

Страница 12: ...be lower than the unit standard value please refer to the nameplate 2 The insulation of water pipe should be done well to prevent energy loss 3 A suitable draining valve should be installed in the bot...

Страница 13: ...Swimming pool heat pump 12 Project Installation sketch map...

Страница 14: ...e neutral ground via a distribution board with fuses If an insulation test is to be carried out in the building please make sure to disconnect the heat pump To avoid the possibility of false action ca...

Страница 15: ...Swimming pool heat pump 14 Circuit diagram Model DSP 45HCA DSP 65HCA DSP 85HCA DSP 100HCA DSP 120HCA...

Страница 16: ...Swimming pool heat pump 15 Model DSP 180HCA 3 DSP 230HCA 3 DSP 260HCA 3...

Страница 17: ...ON or OFF at any state At the ON state press the key into OFF state it shows Clock Working mode and Timer status At the OFF state press the key to start unit it shows Water inlet temp Working mode and...

Страница 18: ...quiry interface of parameter and state it exits inquiry interface to enter into main interface if there is no any operation for 8 seconds 1 3 System parameter setting 1 3 1 At inquiry interface if it...

Страница 19: ...election parameter 0 Only cold 1 Heat pump 2 E heater 3 Only heat 1 Adjustable 09 Water pump working Mode 0 Normal 1 Special 0 Adjustable 10 Automatic return water temp setting value 8 60 40 Adjustabl...

Страница 20: ...is only valid remote controller Parameter table LCD or LED Parameter Meaning Range Default Remark 00 or 0 Cooling return water temp setting value 8 28 12 Adjustable 01 or 1 Heating return water temp...

Страница 21: ...mp difference protection PP 06 or PP 6 Bright Cooling anti freezing protection PP 07 or PP 7 Bright Winter first grade anti freezing protection PP 07 or PP 7 Extinguish Winter second grade anti freezi...

Страница 22: ...does not occur Discharge the water at the bottom of water pump if the unit will not be used for an extended period of time Check the unit thoroughly and fill the system with water fully before using...

Страница 23: ...ire 4 Replace it with new high pressure switch 5 It is done by professionals EE 02 or EE 2 Low pressure protection 1 Check the connecting wire 2 Check if low pressure switch is broken 3 Check if lack...

Страница 24: ...DAISHIBA Heating Refrigeration Equipment Co Ltd Web www daishiba com cn Tel 86 757 85213698 Fax 86 757 85213699 Email jenny daishiba com cn Add No 2 Chuangye Nan Road Songxia Industrial Park Songgang...

Отзывы: