Installation Guide

Daintree

®

 Networked General Purpose Adapter (WGA100)

8

All devices, including wireless adapters must be tested for 

proper operation.
After setting the DIP switches for your application, mounting, 

wiring low voltage, wiring line voltage, powering up and resetting 

the unit, perform the Installation Test. The Installation Test mode

automatically times out after 5 minutes of no activity.

Complete Installation Tests

Successful commissioning is dependent on testing each 

wireless-adapted device at the time of installation. Finding 

installation issues or device problems earlier saves significant 

time during the commissioning process.

To enable the WGA100 test mode, press the blue reset 

button once.
The test mode sequentially tests each enabled device (DIP 

switches that are ON).
If the device is not enabled (DIP switch is off), the system simply 

moves on to the next enabled device.
To exit testing, press and immediately release the reset button. 

You may need to do this several times to cycle through the 

remaining enabled device tests.

If you have not already done so, be sure that each wireless 

adapter’s IEEE address (last 4 or 5 digits) is recorded on the 

facility floor plan. You can use the 4 or 5 digit “Plan” label 

supplied with the WGA100 or you can write the last 4 or 5 digits 

on the floor plan. This information will be used during the 

commissioning process.
After the installation is complete, a marked-up copy of the facility 

floor plan showing the identity and location of each wireless 

adapter (including associated devices) should be available. 

This will simplify and expedite the commissioning process.

7

8

9

Installation Tests

WGA100 Installation Test Mode

Record IEEE Addresses

After the Installation Test is complete the WGA100 is ready to 

communicate with the Daintree Wireless Area Controller (WAC) 

and the Daintree Controls Software (DCS) web-based user 

interface. Upon commissioning, the WGA100 “Join” LED turns 

on solid and remains on as long as the WGA100 is included in 

the ZigBee Network.
After joining the network, the control signals to and from the 

low voltage devices pass through the WGA100 and are sent 

wirelessly to the Daintree Networked. Depending on the zone 

and device configuration in DCS, wireless signals from the 

WAC to the WGA100 determine the operation of the 

associated devices.
For more information about configuring the lighting control 

network, see the instructions and online help provided with 

the Daintree Controls Software web application.

10

Joining the ZigBee Lighting Control Network

 

1

 

Switched Line  

Relay output toggles on and off every 

 

 

voltage relay 

30 seconds for as long as the test mode

 

 

control Binary 

is active. Press the reset button once to

 

 

Output 

move on to the next enabled device.

 

2

 

Binary 

Binary output toggles on and off every 

 

 

Output 

30 seconds for as long as the test mode

 

 

 

is active. Press the reset button once to

 

 

 

move on to the next device.

 

3

 

Analog 

This device is not tested, regardless

 

 

(Multi-state) 

of  whether it is enabled or not.   

 

   Output

 

4

 

Binary Input 

If the binary input is high, the ‘joined’ led   

 

 

(blue wire) 

on the WGA turns on. Otherwise, it stays

 

 

 

off. Press the reset button once to move

 

 

 

on to the next device.

 

5

 

Binary Input 

If the binary input is high, the ‘joined’ led   

 

 

(yellow wire) 

on the WGA turns on. Otherwise, it stays

 

 

 

off. Press the reset button once to move   

 

 

 

on to the next device.

 

6

 

Analog 

The ‘joined’ led on the WGA flashes at 

 

 

 

(Multi-state) 

a frequency proportional to the input

 

 

Input 

voltage. Press the reset button once to 

 

 

 

 

exit the test mode.

Dip 

Switch  

Enabled    Purpose  

Expected Test Mode Response

Содержание GE current WGA100

Страница 1: ...an AC powered device that provides On Off switching and 0 10V analog control as well as reporting and monitoring capability of binary and 0 10V analog signal inputs for non lighting applications It pr...

Страница 2: ...valve or damper actuator An example is a hot water valve opening up 25 to maintain a set point Switch 4 Binary Input Low voltage Blue wire A binary input indicates if a device is turned on or not Some...

Страница 3: ...of the devices connected to it Risk of electrical shock Disconnect all power before installation and during servicing Do not open WGA100 enclosure no user serviceable parts inside All installation and...

Страница 4: ...Guide Daintree Networked General Purpose Adapter WGA100 4 4 Wiring Continued Figure 5 Switched Line Voltage to Contactor Binary Output DIP Switch 1 On Figure 6 Low Voltage On Off LSD Binary Output DIP...

Страница 5: ...General Purpose Adapter WGA100 5 4 Wiring Continued Figure 7 Setback Thermostat Binary Output DIP Switch 2 On Figure 8 Analog Output 0 10V level controllable multistate DIP Switch 3 On Figure 9 Binary...

Страница 6: ...Continued Figure 10 Analog Input 0 10V level monitoring multistate DIP Switch 6 On Figure 11 Combination of Interfaces The interfaces can be enabled in any combination DIP Switches 1 3 4 5 and 6 are t...

Страница 7: ...ough a knockout When the wiring connections have been decided and extra unused wires identified secure the unused wires to keep them neat out of the way and protected against shorting or interference...

Страница 8: ...d IEEE Addresses After the Installation Test is complete the WGA100 is ready to communicate with the Daintree Wireless Area Controller WAC and the Daintree Controls Software DCS web based user interfa...

Страница 9: ...red operation CAN ICES 005 B NMB 005 B FCC Warning Message Industry Canada IC Warning Message Input Voltage 120 277VAC 50 60Hz Switched Output 15A 120 277 VAC Relay 1 hp 120 230 VAC Low Voltage 24VDC...

Отзывы: