3
1
10
• VRV Systems • Outdoor Units
85
• Outdoor Units • HEAT PUMP • RWEYQ-MY1
10
Installation of outdoor units
10 - 3 Selection of location
C
AUTION
1
An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examine where to install the main air conditioner and
electric wires, keeping proper distances away from stereo equipment, personal computers, etc.
햲
Indoor unit
햳
Branch switch, overcurrent breaker
햴
Remote controller
햵
Cool/heat selector
햶
Personal computer or radio
If the electric wave of AM broadcasting is particularly weak, keep distances of 3m or more and use conduit tubes for power and transmission lines.
2
Water quality
Water containing high level of foreign materials may cause the corrosion of heat exchanger and piping or scale accumulation.
Use water satisfying “10-7-4 Water quality”.
3
Cooling tower
Use a closed type cooling tower without fail. (Open type tower cannot be used.)
4
Strainer
Install a strainer (an optional accessory) without fail at the inlet of water piping. (If sands, wastes, rust particles, etc. are mixed in the water
circulation system, damage to the plate type heat exchanger may be caused by the corrosion of metal materials and clogging of the heat
exchanger.)
5
The refrigerant R410A itself is nontoxic, nonflammable and is safe. If the refrigerant should leak however, its concentration may exceed the
allowable limit depending on room size. Due to this it could be necessary to take measures against leakage.
Refer to the chapter “Caution for refrigerant leaks”.
10 - 4 Inspecting and handling the unit
At delivery, the package should be checked and any damage should be reported immediately to the carrier claims agent.
When handling the unit, take into account the following:
1
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
2
Choose the path along which the unit is to be brought in ahead of time.
3
In order to prevent any damage to the unit during installation, use slings (cloth) or patch plates and lift the unit referring to the figure below.
4
Lift the unit preferably with a crane and 2 belts of at least 4m long.
5
Use patch plates or clothes where the belt may hit the casing in order to prevent the casing from being damaged.
6
Be sure use the standard supplied accessories and dedicated parts as installation parts.
햲
Patch plates or clothes
햳
Belt sling
N
OTE
Use belt sling of 20mm width or less which adequately bears the weight of the product.