3
English
1.3. Indoor capacity range
1.3.1. Connection Ratio
Connection Ratio = Total capacity index of the indoor units / Capac-
ity index of the outdoor units
Type
Min. connection ratio
Types of connected outdoor units
RXYQ-A type
Single outdoor unit
6 - 14 ton
50%
16 - 20 ton
Double outdoor units
Type
Max. connection ratio
Types of connected indoor units
When using only
FXDQ, FXMQ-PB,
FXAQ, FXSQ07-54T
When using at least one
FXFQ07/09, FXZQ05T,
FXSQ05T
When using other
indoor unit models
Single
outdoor
unit
6 - 14 ton
200% *1
180% *1
200% *1
16 - 20 ton
180% *1
180% *1
Double outdoor units
160% *1
160% *1
Type
Max. connection ratio
Types of connected air treatment
Low-temperature
hydrobox
When FXMQ-MF is
only connected
When FXMQ-MF
and indoor units are
connected
When HXY48T and
indoor units are
connected
Single
outdoor
unit
6 - 14 ton
100%
100% *2
130% *3
16 - 20 ton
Double outdoor units
Notes:
*1. If the operational capacity of indoor units is more than
130%, low airflow operation is enforced in all the indoor
units. This limitation can be abolished through field setting.
*2. When outdoor-air processing units (FXMQ-MF) and
standard indoor units are connected, the total connection
capacity of the outdoor-air processing units (FXMQ-MF)
must not exceed 30% of the capacity index of the outdoor
units. And the connection ratio must not exceed 100%.
*3. When connecting the hydrobox, to prevent temporary
water temperature drop on the secondary side of the
hydrobox at the time of defrosting or when the indoor unit
starts/stops, and to prevent freezing, connect the indoor
unit with 50% or more capacity of the outdoor unit.
1.3.2. Outdoor Unit Combinations
Total capacity of indoor units needs to be within the specified range.
RXYQ-A type
<Outdoor unit>
<Total capacity index of indoor units>
RXYQ72AATJ*/AAYD*
. . . . . . . . . . . . 36-93
RXYQ96AATJ*/AAYD*
. . . . . . . . . . . . 48-124
RXYQ120AATJ*/AAYD*
. . . . . . . . . . . . 60-156
RXYQ144AATJ*/AAYD*
. . . . . . . . . . . . 72-187
RXYQ168AATJ*/AAYD*
. . . . . . . . . . . . 84-218
RXYQ192AATJ*/AAYD*
. . . . . . . . . . . . 96-249
RXYQ216AATJ*/AAYD*
. . . . . . . . . . . . 108-280
RXYQ240AATJ*/AAYD*
. . . . . . . . . . . . 120-312
RXYQ264AATJ*/AAYD*
. . . . . . . . . . . . 132-343
RXYQ288AATJ*/AAYD*
. . . . . . . . . . . . 144-374
RXYQ312AATJ*/AAYD*
. . . . . . . . . . . . 156-405
RXYQ336AATJ*/AAYD*
. . . . . . . . . . . . 168-436
RXYQ360AATJ*/AAYD*
. . . . . . . . . . . . 180-468
RXYQ384AATJ*/AAYD*
. . . . . . . . . . . . 192-499
RXYQ408AATJ*/AAYD*
. . . . . . . . . . . . 204-530
RXYQ432AATJ*/AAYD*
. . . . . . . . . . . . 216-561
RXYQ456AATJ*/AAYD*
. . . . . . . . . . . . 228-592
RXYQ480AATJ*/AAYD*
. . . . . . . . . . . . 240-624
NOTE
Higher capacity than the table 1.3.2 can be selected, this may affect
heating and cooling capacity. For additional information see technical
engineering data.
1.4. Scope of the manual
This manual describes the procedures for handling, installing and
connecting the VRV RXYQ-A series outdoor units. This manual has
been prepared to ensure adequate maintenance of the unit, and it will
provide help in case problems occur.
INFORMATION
The installation of the indoor unit(s) is described in the indoor unit
installation manual provided with the indoor unit(s).
2. Accessories
2.1. Accessories supplied with this unit
Confirm the following accessories are included. The storage location
of the accessories is shown in the figure below.
Accessories assy (piping)
Accessories assy
(operation and installation manual)
NOTE
Do not throw away any of the accessories until installation is complete.
They are needed for installation work.
Name
Clamp
Manuals, etc.
L type
accessory joint
Quantity
7 pcs.
1 pc. each
1 pc.
Shape
• Operation Manual
• Installation Manual
• REQUEST FOR THE INDICATION label
(Installation records)
Name
Liquid side
accessory
pipe (1)
Liquid side
accessory
pipe (2)
Gas side
accessory
pipe (1)
Gas side
accessory
pipe (2)
Quantity
1 pc.
1 pc.
1 pc.
1 pc.
Shape
96A
168A
72, 96A 120,144A 168-240A
72A 96A 120,144A 240A
01_EN_Main_VRV6_HP_IM.indd 3
01_EN_Main_VRV6_HP_IM.indd 3
2022/12/08 17:55:30
2022/12/08 17:55:30