operation can restart. It will be indicated in below explanations.

 [2-0]=   Cool/Heat selection setting

Cool/Heat selection setting is used in case the optional
Cool/Heat selector (KRC19-26A) is used. Depending on the 
outdoor unit setup (single outdoor unit setup or multi outdoor 
unit setup), the correct setting should be chosen. More 
details on how to use the Cool/Heat selector option can be 
found in the manual of the Cool/Heat selector.
Default value=0.

•  0=Each individual outdoor unit can select Cool/Heat opera-

tion (by Cool/Heat selector if installed), or by defining mas

-

ter indoor user interface (see setting [2-83] on page 39).

•  1=Master unit decides Cool/Heat operation when outdoor 

units are connected in multiple system combination

•  2=Sub unit for Cool/Heat operation when outdoor units 

are connected in multiple system combination

Change [2-0]=0, 1 or 2 in function of required functionality.

[2-4]=  

Phased installation setting

Default value=0.

Value

[2-4]

Description

0

OFF (default)

1

ON

Conditions/rules apply for this setting. Refer to selection 
software or contact your Daikin sales representative for 
further details.

[2-6]=  

Forced operation of indoor unit
Default value=0.

Value 

[2-6]

Description

0

OFF (default)

1

ON

[2-8]= T

e

 target temperature during cooling operation

Default value=2.

Value 

[2-8]

T

e

 target

0

Auto

2

43°F (6°C) (default)

3

45°F (7°C)

4

46°F (8°C)

5

48°F (9°C)

6

50°F (10°C)

7

52°F (11°C)

Change [2-8]=0, 2-7 in function of required operation 
method during cooling.
For more information and advice about the effect of these 
settings, see 15.3. Energy saving and optimum operation on 

page 41.

[2-9]=  

T

c

 target temperature during heating operation

Default value=6.

Value 

[2-9]

T

c

 target

0

Auto

1

106°F (41°C)

3

109°F (43°C)

6

115°F (46°C) (default)

Change [2-9]=0, 1, 3 or 6 in function of required operation 
method during heating.
For more information and advice about the effect of these 
settings, see 15.3. Energy saving and optimum operation on 

page 41.

[2-11]=   Eco level setting for Eco mode via External control adaptor 

(Optional).

Value 
[2-11]

Meaning

Level

0

Inactive (Default)

1

Eco mode active by low 

noise terminal short-

circuit

Standard

2

Eco mode active by 

demand terminal short-

circuit

2-C short circuit = Low

3-C short circuit = Standard

Eco mode can be activated by short circuit the terminal on 
External control adaptor (Optional) according to [2-11] set-
ting. ([2-23] should be “0”)
This unit can operate with “T

e

 or T

c

 fix control” and “Eco 

mode”. Eco mode means “VRT” control.
If the terminal on external control adapter is not connected 

by short circuit with [2-11]≠0, the system operates according 

to [2-8] or [2-9] setting.

[2-12]=  Enable the low noise function and/or power consumption 

limitation via external control adaptor (DTA104A62)

If the system needs to run under low noise operation or 
under power consumption limitation conditions when an 
external signal is sent to the unit, this setting should be 
changed. This setting will only be effective when the optional 
external control adaptor (DTA104A62) is installed.
Default value=0.
To activate this function change [2-12]=1.

[2-18]=   Fan high static pressure setting

In order to increase the static pressure the outdoor unit fan 
is delivering, this setting should be activated. For details 

about this setting, see technical specifications.

Default value=0.
To activate this function change [2-18]=1.

[2-20]=  Additional refrigerant charge

In order to activate the additional refrigerant charge amount, 
the following setting should be applied.
Default value=0.
To activate additional refrigerant charge [2-20]=1.
Further instructions can be found in chapter 14.3. Method for 

adding refrigerant on page 31.

To stop the additional refrigerant charge operation (when 
the required additional refrigerant amount is charged), push 
BS3. If this function was not aborted by pushing BS3, the 
unit will stop its operation after 30 minutes. If 30 minutes was 

not sufficient to add the needed refrigerant amount, the func

-

tion can be reactivated by changing the field setting again.

[2-21]=   Refrigerant recovery/vacuuming mode

In order to achieve a free pathway to recovering refrigerant 
out of the system or to remove residual substances or to 
vacuum the system it is necessary to apply a setting which 
will open required valves in the refrigerant circuit so the 
recovering of refrigerant or vacuuming process can be done 

01_EN_Main_VRV6_HP_IM.indd   37

01_EN_Main_VRV6_HP_IM.indd   37

2022/11/21   10:59:12

2022/11/21   10:59:12

Содержание VRV RXYQ72AATJ Series

Страница 1: ...aikinac com content resources manuals for the most current version of installation instructions In the event of conflicting information the online installation instruction is to be used Veuillez visit...

Страница 2: ...rdance with this in stallation manual Improper installation may result in water leakage electric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentrat...

Страница 3: ...tdoors or indoors Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil spray or vapor is pro duced for example in a kitchen Plastic parts may d...

Страница 4: ...ping length limitations 12 8 Precautions on refrigerant piping 17 8 1 Caution for brazing 17 8 2 Connecting the refrigerant piping 17 8 3 Guidelines for handling stop valve 21 9 Field wiring 21 9 1 Po...

Страница 5: ...YQ 120 240 single modules as indicated 72 96 120 144 168 192 216 240 RXYQ72AATJ AAYD 1 RXYQ96AATJ AAYD 1 RXYQ120AATJ AAYD 1 RXYQ144AATJ AAYD 1 RXYQ168AATJ AAYD 1 RXYQ192AATJ AAYD 1 RXYQ216AATJ AAYD 1...

Страница 6: ...ype Outdoor unit Total capacity index of indoor units RXYQ72AATJ AAYD 36 93 RXYQ96AATJ AAYD 48 124 RXYQ120AATJ AAYD 60 156 RXYQ144AATJ AAYD 72 187 RXYQ168AATJ AAYD 84 218 RXYQ192AATJ AAYD 96 249 RXYQ2...

Страница 7: ...strong enough to support the weight of the unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for main...

Страница 8: ...n the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the unit If...

Страница 9: ...olt holes 9 16 15 7 8 22 5 oblong holes 4 2 Pitch of foundation bolt holes 30 3 16 766 42 3 8 1076 62 7 16 1586 3 Pitch of foundation bolt holes 28 7 16 29 722 737 4 2 7 16 62 5 2 7 16 62 6 30 1 8 765...

Страница 10: ...2 or more Service space h1 2 or more h1 b Service space 2 a 59 1 16 in 1500 mm b 19 11 16 in 500 mm In case of an installation site where sides A B C D have obsta cles the wall heights of sides A C ha...

Страница 11: ...n to the position of the unit s center of gravity NOTE Use a belt sling of 13 16 in 20 mm wide that adequately bears the weight of the unit CAUTION Lift the unit with caution as the unit s center of g...

Страница 12: ...Q192 240 type 62 7 16 in 1586 mm 8 Distance between foundation bolt holes RXYQ72 type 15 1 16 in 383 mm RXYQ96 168 type 21 3 16 in 538 mm RXYQ192 240 type 31 1 4 in 793 mm 9 1 Hole for foundation bolt...

Страница 13: ...mplies with national and local laws For piping work follow the maximum tolerated length difference in height and length after a branch indicated in the 7 5 System piping length limitations on page 12...

Страница 14: ...g between BP unit and Mini split indoor unit G Only in case Mini split indoor units are connected Indoor unit capacity index Gas pipe Liquid pipe 07 09 12 3 8 in 9 5 mm 1 4 in 6 4 mm 15 1 2 in 12 7 mm...

Страница 15: ...downstream of REFNET headers Indoor unit total capacity at REFNET joints accord ing to the REFNET header are as follows REFNET joint Downstream of REFNET joint Indoor unit REFNET header Indoor unit R...

Страница 16: ...xample 2 2 1 a b c d j i A 1 2 3 4 5 6 7 8 H2 e f g h H1 Example 1 2 2 a t s H3 b c d j i A 1 2 3 4 5 6 7 8 H2 e f g h H1 Example 2 2 2 Branch with REFNET header a c b d e f i g h 1 2 3 4 5 6 7 8 H1 H...

Страница 17: ...1 4 in 31 8 mm 1 RXYQ168 216A type 5 8 in 15 9 mm 3 4 in 19 1 mm RXYQ240A type Increase is NOT allowed RXYQ264 336A type 1 3 8 in 34 9 mm 1 1 2 in 38 1 mm 1 3 4 in 19 1 mm 7 8 in 22 2 mm RXYQ360 480A...

Страница 18: ...m 33 ft 10 m 540 ft 165 m See 2 35 Height difference setting on page 38 2 49 Height difference setting on page 39 Table C Refrigerant charge limits when 295 H1 361 Outdoor unit capacity type Additiona...

Страница 19: ...ndoor unit 8 The nearest indoor unit 1 a b c d e f g p a h 130 ft 40 m 7 5 3 System containing VRV indoor units and Mini split indoor units System setup H5 H4 a c f e h H1 BP1 6 i j g b d A B 7 k l BP...

Страница 20: ...eak Use Dry Nitrogen to perform a gas leak detection After cutting the slit holes it is recommended to remove burrs in the slit holes and paint the edges and areas around the edges using the repair pa...

Страница 21: ...12 Field piping 13 Gas flow 14 Stop valve service port A Valve A B Valve B 3 Recover gas and oil from the pinched piping by using a recovery unit CAUTION Do not vent gases into the atmosphere 4 When...

Страница 22: ...onnection from the stop valves to the field piping can be done by us ing accessory pipes supplied as accessory NOTE Make sure that the onsite piping does not come in contact with other piping the bott...

Страница 23: ...r REFNET header for multiple connections of indoor units and others other than outdoor units REFNET joint Mount the REFNET joint so that it branches either horizontally within 30 or vertically 3 0 Hor...

Страница 24: ...ield wiring and components must be installed by a licensed elec trician and must comply with relevant local and national regulations Be sure to use a dedicated power circuit Never use a power supply s...

Страница 25: ...AWG18 16 AWG18 16 AWG18 16 AWG18 16 AWG18 16 RXYQ72AAYD RXYQ96AAYD RXYQ120AAYD RXYQ144AAYD RXYQ168AAYD RXYQ192AAYD RXYQ216AAYD RXYQ240AAYD RXYQ264AAYD RXYQ288AAYD RXYQ312AAYD RXYQ336AAYD RXYQ360AAYD...

Страница 26: ...ire 7 To outdoor unit of other system 8 Use duplex wires No polarity 9 Indoor unit The outdoor unit that connect the transmission wiring to an indoor unit is Master unit of the multi system And the ot...

Страница 27: ...ircuit board of the master unit The outdoor unit that connects transmission wiring to indoor unit is the master unit The others are sub unit 9 5 Power wiring connection procedure Be sure to connect th...

Страница 28: ...er and trans mission wiring using the included clamp Wire so that the ground wiring does not come into contact with the compressor lead wiring If they touch this may have an adverse effect on other de...

Страница 29: ...the front panel of the outdoor unit for details on the location of the service port see the figure below R410A Label See 14 3 Method for adding refrigerant on page 31 for details on handling the stop...

Страница 30: ...riorated Measure the insulation and check the insulation is above regular value in accordance with relevant local and national regulations For those doing pipe work 1 Make sure piping size is correct...

Страница 31: ...ndication as indicated When above situation cannot be confirmed after 12 minutes the error code can be checked on the indoor unit user interface and the outdoor unit segment display Solve the error co...

Страница 32: ...return to the default situation when shipped from factory 13 2 2 Operating the DIP switches By operating the DIP switches it is possible to What to do with DIP switch DS1 1 Cool Heat selector refer t...

Страница 33: ...0 kg unit RXYQ 120A type 0 0 lbs unit 0 0 kg unit RXYQ 144A type 3 4 lbs unit 1 5 kg unit RXYQ 168A type 3 9 lbs unit 1 8 kg unit RXYQ 192A type 18 5 lbs unit 8 4 kg unit RXYQ 216A type 18 7 lbs unit...

Страница 34: ...15 4 Test opera tion on page 43 R Q You want to execute automatic refrigerant charge B A Step 4b 5 Manual refrigerant charging method in cooling operation NO YES Step 4b 5 Automatic refrigerant charg...

Страница 35: ...on to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not Charge the liquid refrigerant with the cylinder in upright positio...

Страница 36: ...step is included in below procedure This step can be skipped charging will take longer in such a case Follow the steps as described below and take into account whether you want to use the automatic ch...

Страница 37: ...ge or E 3 in case the out door temperature is out of range In this case when the additional refrigerant charging was not finished step 6A has to be repeated INFORMATION When a malfunction is detected...

Страница 38: ...s applicable DANGER ELECTRICAL SHOCK See Safety considerations on page i 15 1 Checks before initial start up After the installation of the unit first check the following items Once all below checks ar...

Страница 39: ...tion of the unit compared to nominal operating conditions Power consumption limitation can be set in mode 2 There are two methods to activate power consumption limitation of the outdoor unit system T...

Страница 40: ...rcuit Standard 2 Eco mode active by demand terminal short circuit 2 C short circuit Low 3 C short circuit Standard Eco mode can be activated by short circuit the terminal on External control adaptor O...

Страница 41: ...conditions when an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 1 The level is according to the table Default value 3...

Страница 42: ...n and advice about the effect of these settings see 15 3 Energy saving and optimum operation on page 41 2 83 Master user interface allocation in case VRV indoor units and Mini split indoor units are u...

Страница 43: ...ump lockout release differential Heat pump would be resumed when the outdoor ambient temp is recovered by differential below above the Heat Pump Lockout Temp Value 2 47 Fahrenheit F Celsius C 0 5 2 8...

Страница 44: ...n nected indoor unit type E g when your system is operating in heating you do not need as much heating under high outdoor ambient temperatures e g 68 F 20 C as under low outdoor ambient temperatures e...

Страница 45: ...of cooling operation the evaporating temperature is allowed to go down to 43 F 6 C on temporary base depending on the situation In case of heating operation the condense temperature is allowed to go u...

Страница 46: ...r purge etc See installation manual of the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will caus...

Страница 47: ...5 seconds or more The unit will start test operation The test operation is automatically carried out the outdoor unit display will indicate 01 and the indication Test operation and Under centralized c...

Страница 48: ...A8P X8A Check connection on printed circuit board or actuator 26 27 Electronic expansion valve malfunction Y4E A1P X25A Check connection on printed circuit board or actuator 29 34 Electronic expansion...

Страница 49: ...A Check connection on printed circuit board or actuator 07 09 High pressure sensor malfunction short circuit S1NPH A1P X32A Check connection on printed circuit board or actuator JC 06 08 Low pressure...

Страница 50: ...ch R407C Mini split etc Check if other indoor units have malfunction and con firm indoor unit mix is allowed 18 20 Wrong combination different series e g RXYQ and REYQ or different type e g A type and...

Страница 51: ...ester 3 White connector 3 To prevent damaging the printed circuit board touch a noncoated metal part to eliminate static electricity before pulling out or plug ging in connectors 4 Pull out junction c...

Страница 52: ...directly related to the humanly occupied space in to which it could leak The unit of measurement of the concentration is lbs ft 3 kg m3 the weight in lbs kg of the refrigerant gas in 1 ft 3 1 m3 volu...

Страница 53: ...Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 3P657316 2F EM22A039 2212 SP 00_CV_VRV6_HP_IM indd 2 00_CV_VRV6_HP_IM indd 2 2022 12 14 18 06 05 2022 12 14 18 06 05...

Отзывы: