
EDUS341411-N
Installation Manual
Installation of Outdoor Units
45
3P362438-1B
35
3P362438-1B English
[2-34]=
Indoor unit fan tap setting
Indoor units fan speed limitation related to connection ca-
pacity and outdoor air temperature for energy saving.
Default value=0
Value
[2-34]
Indoor unit fan tap setting
0
Fan speed is limited to L tap when indoor units
ECRCEKV[ű
1
In heating mode, fan speed is limited to L tap
YJGPKPFQQTWPKVUECRCEKV[ű
2
Fan speed follows a setting of the remote
controller (not limited by indoor units connection
capacity).
3
Fan speed is limited to L tap when outdoor
air temperature goes down to below 85.1°F
(29.5°C). It returns to remote controller setting
when outdoor air temperature goes up to over
90.5 °F (32.5°C).
4
Fan speed is limited to L tap when outdoor
air temperature goes down to below 74.3°F
(23.5°C). It returns to remote controller setting
when outdoor air temperature goes up to over
79.7°F (26.5°C).
5
Fan speed is limited to L tap when outdoor
air temperature goes down to below 66.7°F
(19.3°C). It returns to remote controller setting
when outdoor air temperature goes up to over
72.1°F (22.3°C).
[2-35]=
Height difference setting
Default value=1
In case the outdoor unit is installed in the lowest position
(indoor units are installed on a higher position than outdoor
units) and the height difference between the highest indoor
WPKVCPFVJGQWVFQQTWPKVGZEGGFUHVOVJGUGVVKPI
[2-35] should be changed to 0.
Other changes/limitations to the circuit apply, for more infor-
mation see 7.5.2. System only containing VRV indoor units
QPRCIG|
[2-49]=
Height difference setting
Default value=0
In case the outdoor unit is installed in the highest position
(indoor units are installed on a lower position than outdoor
units) and the height difference between the lowest indoor
WPKVCPFVJGQWVFQQTWPKVGZEGGFUHVOVJGUGVVKPI
[2-49] has to be changed to 1.
Other changes/limitations to the circuit apply, for more infor-
mation see 7.5.2. System only containing VRV indoor units
QPRCIG|
[2-81]=
Cooling comfort setting
Default value=1
Value
[2-81]
Cooling comfort setting
0
'EQ
1
Mild (default)
2
Quick
3
Powerful
Change [2-81]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8].
For more information and advice about the impact of these
UGVVKPIUUGG'PGTI[UCXKPICPFQRVKOWOQRGTCVKQP
[2-82]=
Heating comfort setting
Default value=1
Value
[2-82]
Heating comfort setting
0
'EQ
1
Mild (default)
2
Quick
3
Powerful
Change [2-82]=0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
For more information and advice about the impact of these
UGVVKPIUUGG'PGTI[UCXKPICPFQRVKOWOQRGTCVKQP
[2-83]=
Master user interface allocation in case VRV indoor units
and Mini-split indoor units are used at the same time
By changing setting [2-83], you can allow the VRV indoor
unit to be the operation mode selector (system power OFF/
ON is required after applying this setting).
r
[2-83]=1 Mini-split indoor unit has mode selection right
(default setting).
r
[2-83]=0 VRV indoor unit has mode selection right.
15.3. Energy saving and optimum operation
This VRV IV heat pump system is equipped with advanced energy
saving functionality. Depending on the priority, emphasizes can be
put on energy saving or comfort level. Several parameters can be se-
lected, resulting in the optimal balance between energy consumption
and comfort for the particular application.
5GXGTCNRCVVGTPUCTGCXCKNCDNGCPFGZRNCKPGFDGNQY/QFKH[VJGRC
-
rameters to the needs of your building and to realize the best balance
between energy consumption and comfort.
15.3.1.
Three main operation methods are available:
r
Basic
6JGTGHTKIGTCPVVGORGTCVWTGKUƂZGFKPFGRGPFGPVHTQOVJGUKVWCVKQP
It corresponds to the standard operation which is known and can be
GZRGEVGFHTQOWPFGTRTGXKQWU848U[UVGOU
r
To activate this operation method under cooling operation:
EJCPIGƂGNFUGVVKPI=?
r
To activate this operation method under heating operation:
EJCPIGƂGNFUGVVKPI=?
r
Automatic
The refrigerant temperature is set depending on the outdoor ambi-
ent conditions. As such adjusting the refrigerant temperature to
match the required load (which is also related to the outdoor ambi-
ent conditions).
'IYJGP[QWTU[UVGOKUQRGTCVKPIKPEQQNKPI[QWFQPQVPGGFCU
much cooling under low outdoor ambient temperatures (e.g., 77°F
(25°C)) as under high outdoor ambient temperatures (e.g., 95°F
(35°C)).
Using this idea, the system automatically starts increasing its refrig-
erant temperature, automatically reducing the delivered capacity
CPFKPETGCUKPIVJGU[UVGOoUGHƂEKGPE[
r
To activate this operation method under cooling operation:
EJCPIGƂGNFUGVVKPI=?FGHCWNV
'IYJGP[QWTU[UVGOKUQRGTCVKPIKPJGCVKPI[QWFQPQVPGGFCU
much heating under high outdoor ambient temperatures (e.g., 59°F
(15°C)) as under low outdoor ambient temperatures (e.g., 23°F
(–5°C)).
Содержание VRV IV RXYQ TTJU Series
Страница 1: ...EDUS341411 N Installation...
Страница 61: ...REFNET Joint and Header EDUS341411 N 62 Installation of Outdoor Units KHRP26M72TU KHRP26M73TU 3P161697D...
Страница 62: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 63 3P161697D...
Страница 66: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 67 C 3P113151C 7 8 1 1 1 8...
Страница 67: ...REFNET Joint and Header EDUS341411 N 68 Installation of Outdoor Units KHRP26M73HU 3P185500...
Страница 68: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 69 3P185500...
Страница 70: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 71 1P218719...
Страница 71: ...REFNET Joint and Header EDUS341411 N 72 Installation of Outdoor Units 1P218719...
Страница 72: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 73 1P218720...
Страница 73: ...REFNET Joint and Header EDUS341411 N 74 Installation of Outdoor Units 1P218720...
Страница 75: ...REFNET Joint and Header EDUS341411 N 76 Installation of Outdoor Units 1P280278A...
Страница 76: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 77 1P280278A...
Страница 77: ...REFNET Joint and Header EDUS341411 N 78 Installation of Outdoor Units 1P280279...
Страница 78: ...EDUS341411 N Caution Label Installation of Outdoor Units 79 6 Caution Label 6 1 RXYQ72TYDN RXYQ72TTJU 2P361359C...
Страница 79: ...Caution Label EDUS341411 N 80 Installation of Outdoor Units 2P361359C...
Страница 80: ...EDUS341411 N Caution Label Installation of Outdoor Units 81 3P357947A...
Страница 81: ...Caution Label EDUS341411 N 82 Installation of Outdoor Units 3P357947A...
Страница 82: ...EDUS341411 N Caution Label Installation of Outdoor Units 83 6 2 RXYQ96 168TYDN RXYQ96 168TTJU 3P361373...
Страница 83: ...Caution Label EDUS341411 N 84 Installation of Outdoor Units 1P361833B...
Страница 84: ...EDUS341411 N Caution Label Installation of Outdoor Units 85 1P361833B...
Страница 85: ...Caution Label EDUS341411 N 86 Installation of Outdoor Units 1P361833B...
Страница 86: ...EDUS341411 N Caution Label Installation of Outdoor Units 87 1P361833B...
Страница 87: ...Caution Label EDUS341411 N 88 Installation of Outdoor Units 1P361833B...
Страница 88: ...EDUS341411 N Caution Label Installation of Outdoor Units 89 1P361833B...
Страница 89: ...Caution Label EDUS341411 N 90 Installation of Outdoor Units 3P357946A...
Страница 90: ...EDUS341411 N Caution Label Installation of Outdoor Units 91 3P357946A...