Installation of Outdoor Units
3P362438-1B
10
3P362438-1B English
7.3.3. Piping between refrigerant branch kit and BP unit: F
Pipe size for direct connection on BP unit must be based on the total
capacity of the connected indoor units (only in case Mini-split indoor
units are connected).
6QVCNECRCEKV[KPFGZQH
connected indoor units
Gas pipe
Liquid pipe
< 24
1/2 in. (12.7 mm)
1/4 in. (6.4 mm)
Ű
u
< 57
5/8 in. (15.9 mm)
3/8 in. (9.5 mm)
> 57
3/4 in. (19.1 mm)
Example:
&QYPUVTGCOECRCEKV[HQT(ECRCEKV[KPFGZQHWPKVECRCEKV[KPFGZ
of unit 5
7.3.4.
Piping between BP unit and Mini-split indoor unit: G
Only in case Mini-split indoor units are connected.
+PFQQTWPKVECRCEKV[KPFGZ
Gas pipe
Liquid pipe
07, 09, 12
3/8 in. (9.5 mm)
1/4 in. (6.4 mm)
15, 18, 24
1/2 in. (12.7 mm)
7.3.5. Piping between refrigerant branch kit and indoor unit: E
Pipe size for direct connection to indoor unit must be the same as the
connection size of the VRV indoor unit.
Indoor unit
ECRCEKV[KPFGZ
Piping outer diameter size
Gas pipe
Liquid pipe
07, 09, 12, 18
1/2 in. (12.7 mm)
1/4 in. (6.4 mm)
24, 30, 36, 48, 54
5/8 in. (15.9 mm)
3/8 in. (9.5 mm)
72
3.4 in. (19.1 mm)
96
7/8 in. (22.2 mm)
r
When the equivalent pipe length between outdoor and indoor units
is 295 ft. (90 m) or more, the size of the main pipes (both gas side
and liquid side) must be increased. Depending on the length of the
piping, the capacity may drop, but even in such a case it is possible
to increase the size of the main pipes.
r 'XGPCUVJGNGPIVJQHVJGRKRKPIKUNGUUVJCPHVOKVKUCDNG
to increase the diameter of piping to improve performance.
1
5
2
3
4
1 Outdoor unit
2
/CKPRKRGUQWVFQQTWPKVVQƂTUVTGHTKIGTCPVDTCPEJMKV
3 Increase
4 First refrigerant branch kit
5 Indoor unit
Size up for equivalent length for outdoor-indoor units over 295 ft. (90 m)
Outdoor unit capacity
type
Gas pipe
Liquid pipe
RXYQ72T type
3/4 in. (19.1 mm)
o
7/8 in. (22.2 mm)
3/8 in. (9.5 mm)
o
1/2 in. (12.7 mm)
RXYQ96T type
7/8 in. (22.2 mm)
o
1 in. (25.4 mm)
(a)
RXYQ120T type
Increase is NOT allowed
1/2 in. (12.7 mm)
o
5/8 in. (15.9 mm)
RXYQ144T type
1-1/8 in. (28.6 mm)
o
1-1/4 in. (31.8 mm)
(a)
RXYQ168-216T type
5/8 in. (15.9 mm)
o
3/4 in. (19.1 mm)
RXYQ240T type
Increase is NOT allowed
RXYQ264-336T type
1-3/8 in. (34.9 mm)
o
1-1/2 in. (38.1 mm)
(a)
3/4 in. (19.1 mm)
o
7/8 in. (22.2 mm)
RXYQ360-408T type
Increase is NOT allowed
(a) If size is NOT available, increase is NOT allowed.
7.4. Selection of refrigerant branch kits
Refrigerant refnets
(QTRKRKPIGZCORNGTGHGTVQ5GNGEVKQPQHRKRKPIUK\GQPRCIG|
r 9JGPWUKPITGHPGVLQKPVUCVVJGƂTUVDTCPEJHTQOVJGQWVFQQTWPKV
choose from the following table in accordance with the capacity of
VJGQWVFQQTWPKVGZCORNGTGHPGVLQKPVCUGG5GNGEVKQPQHRKRKPI
size).
Outdoor unit capacity type
Kit name
RXYQ 72, 96T type
KHRP26M33T
RXYQ 120-216T type
KHRP26M72TU9
RXYQ 240-408T type
KHRP26M73TU9
r (QTTGHPGVLQKPVUQVJGTVJCPVJGƂTUVDTCPEJGZCORNGTGHPGVLQKPVD
see 7.3. Selection of piping size), select the proper branch kit model
DCUGFQPVJGVQVCNECRCEKV[KPFGZQHCNNKPFQQTWPKVUEQPPGEVGFCHVGT
the refrigerant branch.
+PFQQTWPKVECRCEKV[KPFGZ
Kit name
< 72
KHRP26M22T
Ű
u
< 111
KHRP26M33T
Ű
u
< 246
KHRP26M72TU9
ű
KHRP26M73TU9
r
Concerning refnet headers, choose from the following table in
accordance with the total capacity of all the indoor units connected
below the refnet header.
+PFQQTWPKVECRCEKV[KPFGZ
Kit name
< 72
KHRP26M22H9:
OCZKOWOKPFQQTWPKVU
or
KHRP26M33H9:
OCZKOWOKPFQQTWPKVU
Ű
u
< 111
KHRP26M33H9
Ű
u
< 230
KHRP26M72H9
ű
KHRP26M73H9
Содержание VRV IV RXYQ TTJU Series
Страница 1: ...EDUS341411 N Installation...
Страница 61: ...REFNET Joint and Header EDUS341411 N 62 Installation of Outdoor Units KHRP26M72TU KHRP26M73TU 3P161697D...
Страница 62: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 63 3P161697D...
Страница 66: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 67 C 3P113151C 7 8 1 1 1 8...
Страница 67: ...REFNET Joint and Header EDUS341411 N 68 Installation of Outdoor Units KHRP26M73HU 3P185500...
Страница 68: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 69 3P185500...
Страница 70: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 71 1P218719...
Страница 71: ...REFNET Joint and Header EDUS341411 N 72 Installation of Outdoor Units 1P218719...
Страница 72: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 73 1P218720...
Страница 73: ...REFNET Joint and Header EDUS341411 N 74 Installation of Outdoor Units 1P218720...
Страница 75: ...REFNET Joint and Header EDUS341411 N 76 Installation of Outdoor Units 1P280278A...
Страница 76: ...EDUS341411 N REFNET Joint and Header Installation of Outdoor Units 77 1P280278A...
Страница 77: ...REFNET Joint and Header EDUS341411 N 78 Installation of Outdoor Units 1P280279...
Страница 78: ...EDUS341411 N Caution Label Installation of Outdoor Units 79 6 Caution Label 6 1 RXYQ72TYDN RXYQ72TTJU 2P361359C...
Страница 79: ...Caution Label EDUS341411 N 80 Installation of Outdoor Units 2P361359C...
Страница 80: ...EDUS341411 N Caution Label Installation of Outdoor Units 81 3P357947A...
Страница 81: ...Caution Label EDUS341411 N 82 Installation of Outdoor Units 3P357947A...
Страница 82: ...EDUS341411 N Caution Label Installation of Outdoor Units 83 6 2 RXYQ96 168TYDN RXYQ96 168TTJU 3P361373...
Страница 83: ...Caution Label EDUS341411 N 84 Installation of Outdoor Units 1P361833B...
Страница 84: ...EDUS341411 N Caution Label Installation of Outdoor Units 85 1P361833B...
Страница 85: ...Caution Label EDUS341411 N 86 Installation of Outdoor Units 1P361833B...
Страница 86: ...EDUS341411 N Caution Label Installation of Outdoor Units 87 1P361833B...
Страница 87: ...Caution Label EDUS341411 N 88 Installation of Outdoor Units 1P361833B...
Страница 88: ...EDUS341411 N Caution Label Installation of Outdoor Units 89 1P361833B...
Страница 89: ...Caution Label EDUS341411 N 90 Installation of Outdoor Units 3P357946A...
Страница 90: ...EDUS341411 N Caution Label Installation of Outdoor Units 91 3P357946A...