background image

14 Piping installation

Installation and operation manual

29

RXYQQ8~20U7Y1B
VRV IV Q+ series heat pump
4P546221-1B – 2020.10

i

Liquid line stop valve

j

Outdoor unit

k

To indoor unit

l

Stop valve

m

Field piping

n

Gas flow

o

Stop valve service port

A

Valve A

B

Valve B

C

Valve C

4

Do one of the following:

If

Then

4a

The calculated additional
refrigerant amount is reached
by above pre-charging
procedure

Close valve B and disconnect
the manifold connection to
the liquid line.

4b

The total amount of
refrigerant could not be
charged by pre-charging

Close valve B, disconnect the
manifold connection to the
liquid line, and perform steps
5~6.

INFORMATION

If  the  total  additional  refrigerant  amount  was  reached  in
step  4  (by  pre-charging  only),  record  the  amount  of
refrigerant  that  was  added  on  the  additional  refrigerant
charge  label  provided  with  the  unit  and  attach  it  on  the
back side of the front panel.

Perform 

the 

test 

procedure 

as 

described 

in

"17 Commissioning"

 [

4

 37].

Charging refrigerant

5

After  pre-charging,  connect  valve  A  to  the  refrigerant  charge
port and charge the remaining additional refrigerant through this
port.  Open  all  outdoor  unit  stop  valves.  At  this  point,  valve  A
must remain closed!

INFORMATION

For  a  multi  outdoor  unit  system,  it  is  not  required  to
connect all charge ports to a refrigerant tank.

The  refrigerant  will  be  charged  with  ±22  kg  in  1  hour  time
at an outdoor temperature of 30°C DB or with ±6 kg at an
outdoor temperature of 0°C DB.

If  you  need  to  speed  up  in  case  of  a  multiple  outdoor
system, connect the refrigerant tanks to each outdoor unit.

NOTICE

▪ The refrigerant charging port is connected to the piping

inside  the  unit.  The  unit's  internal  piping  is  already
factory  charged  with  refrigerant,  so  be  careful  when
connecting the charge hose.

▪ After  adding  the  refrigerant,  do  not  forget  to  close  the

lid  of  the  refrigerant  charging  port.  The  tightening
torque for the lid is 11.5 to 13.9 N•m.

▪ In  order  to  ensure  uniform  refrigerant  distribution,  it

may take the compressor ±10 minutes to start up after
the unit has started operation. This is not a malfunction.

14.4.6

Step 6a: To automatically charge
refrigerant

INFORMATION

The automatic refrigerant charging has limits as described
below.  Out  of  these  limits,  the  system  cannot  operate  the
automatic refrigerant charging:

▪ Outdoor temperature: 0~43°C DB.

▪ Indoor temperature: 10~32°C DB.

▪ Total indoor unit capacity: ≥80%.

When  "

  "  or  "

"  starts  flashing  (ready  for  charging),  push

BS2  within  5  minutes.  Open  valve  A.  If  BS2  is  not  pushed  within  5
minutes, a malfunction code will appear:

If

Then

Heating operation

"

" will be flashing. Push BS2 to

restart the procedure.

Cooling operation

Malfunction code "

" will appear. Push

BS1 to abort and restart the procedure.

If

Then

"

", "

", or "

"

appears

Push BS1 to finish the automatic
charging function procedure. The
ambient conditions are favourable to
execute the test run.

"

", or "

" appears

The ambient conditions are NOT
favourable to execute the test run. Push
BS1 to finish the automatic charging
procedure.

INFORMATION

In case a malfunction code occurred during this automatic
charging  procedure,  the  unit  will  stop  and  indicate  "

"

flashing. Push BS2 to restart the procedure.

INFORMATION

▪ When  a  malfunction  is  detected  during  the  procedure

(e.g, in case of closed stop valve), a malfunction code
will  be  displayed.  In  that  case,  refer  to 

"19.1  Solving

problems  based  on  error  codes"

  [

4

  38]  and  solve  the

malfunction accordingly. Resetting the malfunction can
be  done  by  pushing  BS1.  The  procedure  can  be
restarted  from 

"Step  6a:  To  automatically  charge

refrigerant"

 [

4

 29].

▪ Aborting the automatic refrigerant charge is possible by

pushing  BS1.  The  unit  will  stop  and  return  to  idle
condition.

14.4.7

Step 6b: To manually charge refrigerant

INFORMATION

The manual refrigerant charge operation will automatically
stop  within  30  minutes.  If  charging  is  not  completed  after
30  minutes,  perform  the  additional  refrigerant  charging
operation again.

INFORMATION

▪ When  a  malfunction  is  detected  during  the  procedure

(e.g., in case of closed stop valve), a malfunction code
will  be  displayed.  In  that  case,  refer  to 

"Error  codes

when  charging  refrigerant"

  [

4

  30]  and  solve  the

malfunction accordingly. Resetting the malfunction can
be  done  by  pushing  BS3.  The  procedure  can  be
restarted  from 

"Step  6b:  To  manually  charge

refrigerant"

 [

4

 29].

▪ Aborting  the  manual  refrigerant  charge  is  possible  by

pushing  BS3.  The  unit  will  stop  and  return  to  idle
condition.

Содержание VRV IV Q+ Series

Страница 1: ...ion and operation manual VRV IV Q series heat pump English Installation and operation manual VRV IV Q series heat pump RXYQQ8U7Y1B RXYQQ10U7Y1B RXYQQ12U7Y1B RXYQQ14U7Y1B RXYQQ16U7Y1B RXYQQ18U7Y1B RXYQ...

Страница 2: ...iejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin ju...

Страница 3: ...staava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Страница 4: ...8 2 15 Symptom The display shows 88 14 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 14 8 2 17 Symptom The inside of an outdoor unit is warm even whe...

Страница 5: ...tion manual Installation and operation instructions Format Paper in the box of the outdoor unit Installer and user reference guide Preparation of the installation reference data Detailed step by step...

Страница 6: ...NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because t...

Страница 7: ...of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and recovery By ensurin...

Страница 8: ...e WARNING Do NOT modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your dealer In case of accidental...

Страница 9: ...range is only valid in case direct expansion indoor units are connected to the VRV IV system 6 2 Operating the system 6 2 1 About operating the system Operation procedure varies according to the combi...

Страница 10: ...al of the user interface 6 3 Using the dry program 6 3 1 About the dry program The function of this program is to decrease the humidity in your room with minimal temperature decrease minimal room cool...

Страница 11: ...operating in the horizontal direction It may cause dew or dust to settle on the ceiling or flap 6 5 Setting the master user interface 6 5 1 About setting the master user interface c c b b a a VRV rep...

Страница 12: ...from fan heaters gas cookers etc is present Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation 8 Troubleshooting If one...

Страница 13: ...anger gas temperature sensor malfunction outdoor Suction temperature sensor malfunction outdoor De icing temperature sensor malfunction outdoor Liquid temperature sensor after subcool HE malfunction o...

Страница 14: ...s because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication between the units causing them to stop Operation automatical...

Страница 15: ...ESULT OF LEAK CHECK OPERATION REQUEST FOR THE INDICATION OF ADDITIONAL REFRIGERANT CHARGING AND LEAK DETECTION OPERATION RESULT BE SURE TO FILL OUT THE BLANKS WHICH ARE NEEDED FOR AFTER SALE SERVICES...

Страница 16: ...15 C a e c d d c b a VRV IV replacement heat pump outdoor unit b Refrigerant piping c VRV direct expansion DX indoor unit d User interface dedicated depending on indoor unit type e Cool Heat changeov...

Страница 17: ...a b c d e a Electrical component box cover b Front side c Power supply terminal block d Sealing material e Moisture and dirt could enter NOT allowed Allowed 13 3 Mounting the outdoor unit 13 3 1 To p...

Страница 18: ...and thickness and if the pipes and branch piping are not corroded If the existing field piping does not comply with the above conditions replace the existing field piping with field piping that meets...

Страница 19: ...34 9 1 0 38 1 41 3 1 1 a If annealed temper grade is 1 The refrigerant pipes and branches must meet the condition of design pressure 33 bar 3 3 MPa If it is NOT possible to confirm this use the refrig...

Страница 20: ...If the piping length between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line within a length of 2 m from the kit If Then 2 m a b 2 m 2 m a 2 m 2 m 200 mm 200 mm b 2 m 2 m...

Страница 21: ...allowed Allowed Make sure that the total length of the piping connected to the joint is absolute straight for more than 500 mm Only if a straight field piping of more than 120 mm is connected more tha...

Страница 22: ...lve size mm Tightening torque N m when opening or closing Valve body Hexagonal wrench Service port 9 5 5 7 4 mm 10 7 14 7 12 7 8 10 15 9 14 16 6 mm 19 1 19 21 8 mm 25 4 14 2 7 To remove the spun pipes...

Страница 23: ...ant piping involves Checking for any leakages in the refrigerant piping Performing vacuum drying to remove all moisture air or nitrogen in the refrigerant piping If there is a possibility of moisture...

Страница 24: ...our 3 Should you fail to reach the target vacuum within 2 hours or maintain the vacuum for 1 hour the system may contain too much moisture In that case break the vacuum by pressurising with nitrogen g...

Страница 25: ...or manual charging This step is included in below procedure see To charge refrigerant 428 It can be skipped but charging will take longer then A flow chart is available which gives an overview of the...

Страница 26: ...kg 12 HP N 6 C2 0 kg C C1 C2 0 5 kg Metric piping When using metric piping replace the weight factors in the formula by the ones from the following table Inch piping Metric piping Piping Weight facto...

Страница 27: ...t on the additional refrigerant charge label Go to test run Step 4b Close valve B R Q R Q R Q Step 5 Connect valve A to refrigerant charge port Open all outdoor unit stop valves Proceed with automatic...

Страница 28: ...al refrigerant charge label Go to test run Following codes appear e 2 indoor temperature out of range and e 3 outdoor temperature out of range Push BS1 to leave program Charging is finished Fill in th...

Страница 29: ...6 Step 6a To automatically charge refrigerant INFORMATION The automatic refrigerant charging has limits as described below Out of these limits the system cannot operate the automatic refrigerant charg...

Страница 30: ...tial NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in...

Страница 31: ...nd select the next higher recommended fuse capacity Example Combining the RXYQQ30 by using the RXYQQ18 and RXYQQ12 Minimum circuit ampacity of the RXYQQ18 35 0 A Minimum circuit ampacity of the RXYQQ1...

Страница 32: ...or unit e Outdoor unit In case of multi outdoor unit installation F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P d d e f b a c Q1 Q2 a Unit A master outdoor unit b Unit B slave outdoor unit c Unit C slave outdoor unit d...

Страница 33: ...Power supply terminal block f Connect each power wire RED to L1 WHT to L2 BLK to L3 and BLU to N g Earth wire GRN YLW h Tie wrap i Cup washer j When connecting the earth wire it is recommended to perf...

Страница 34: ...he current field setting value and changing the current field setting value is possible In general normal operation can be resumed without special intervention after changing field settings Some field...

Страница 35: ...nit What How Changing and accessing the setting in mode 1 Once mode 1 is selected push BS1 one time you can select the wanted setting It is done by pushing BS2 Accessing the selected setting s value i...

Страница 36: ...et C 0 default Auto 2 6 3 7 4 8 5 9 6 10 7 11 2 9 Tc target temperature during heating operation 2 9 Tc target C 0 default Auto 1 41 3 43 6 46 2 20 Manual additional refrigerant charge 2 20 Descriptio...

Страница 37: ...ce of 2 M or more is attained by applying a voltage of 500 V DC between power terminals and earth NEVER use the megatester for the transmission wiring Fuses circuit breakers or protection devices Chec...

Страница 38: ...egment display idle Abnormal completion Indication of malfunction code on the 7 segment display Refer to 17 5 Correcting after abnormal completion of the test run 438 to take actions for correcting th...

Страница 39: ...rface s display or transmission wiring between the outdoor unit and the indoor unit Electronic expansion valve malfunction main Y1E A1P X21A Check connection on PCB or actuator Electronic expansion va...

Страница 40: ...tuator De icing temperature sensor malfunction R7T A1P X30A Check connection on PCB or actuator Liquid temperature sensor after subcool HE malfunction R5T A1P X30A Check connection on PCB or actuator...

Страница 41: ...alfunction Check if other indoor units have malfunction and confirm indoor unit mix is allowed Connection malfunction over indoor units or type mismatch R410A R407C RA Hydrobox etc Check if other indo...

Страница 42: ...d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm Layout A B C D A B Possibility 1 Possibility 2 5 a 10 mm b 500 mm c 10 mm d 500 mm e 20 mm f 900 mm a 50 mm b 500 mm c 50 mm d 500 mm e 100...

Страница 43: ...ed are listed below INFORMATION The wiring diagram on the outdoor unit is only for the outdoor unit For the indoor unit or optional electrical components refer to the wiring diagram of the indoor unit...

Страница 44: ...ion valve liquid cooling Y1S Solenoid valve main Y2S Solenoid valve accumulator oil return Y3S Solenoid valve oil 1 Z C Noise filter ferrite core Z F A2P A5P Noise filter with surge absorber Connector...

Страница 45: ...expansion valve main Y2E Electronic expansion valve sub cool Y3E Electronic expansion valve liquid cooling Y1S Solenoid valve main Y2S Solenoid valve accumulator oil return Y3S Solenoid valve oil 1 Y4...

Страница 46: ......

Страница 47: ......

Страница 48: ...4P546221 1B 2020 10 Copyright 2018 Daikin 4P546221 1 B 0000000Y Verantwortung f r Energie und Umwelt...

Отзывы: