14 Piping installation
Installation and operation manual
19
RXYQQ8~20U7Y1B
VRV IV Q+ series heat pump
4P546221-1B – 2020.10
▪ Downstream capacity for D=capacity index of unit 1+capacity
index of unit 2
E: Piping between refrigerant branch kit and
indoor unit
Pipe size for direct connection to indoor unit must be the same as
the connection size of the indoor unit.
Indoor unit
capacity
index
Piping outer diameter size (mm)
Gas pipe
Liquid pipe
Standard
Max.
Standard
Max.
15~50
12.7
15.9
6.4
9.5
63, 80
15.9
19.1
9.5
12.7
100~140
25.4
200
19.1
28.6
250
22.2
▪ When the equivalent pipe length between outdoor and indoor
units is 90 m or more, the size of the main pipes (both gas side
and liquid side) must be increased. Depending on the length of the
piping, the capacity may drop, but even in such a case the size of
the main pipes has to be increased. More specifications can be
found in the technical engineering data book.
e
d
b
c
a
a
Outdoor unit
b
Main pipes (increase if the equivalent piping length is
≥90 m)
c
First refrigerant branch kit
d
Piping between refrigerant branch kit and indoor unit
e
Indoor unit
Size up
HP class
Piping outer diameter size (mm)
Gas pipe
Liquid pipe
8
19.1 → 22.2
9.5 → 12.7
10
22.2 → 25.4
(a)
12+14
28.6
(b)
12.7 → 15.9
16
28.6 → 31.8
(a)
18~22
15.9 → 19.1
24
34.9
(b)
26~34
34.9 → 38.1
(a)
19.1 → 22.2
36~42
41.3
(b)
(a)
If the size-up size is NOT available, you must use the standard
size. Sizes bigger than the size-up size are NOT allowed. But
even if you use the standard size, the equivalent piping length is
allowed to be more than 90 m.
(b)
Pipe size-up is NOT allowed.
▪ The pipe thickness of the refrigerant piping shall comply with the
applicable legislation. The minimal pipe thickness for R410A
piping must be in accordance with the table below.
Pipe Ø (mm)
Minimal thickness t (mm)
6.4
0.4
9.5
0.5
12.7
0.7
15.9
0.9
19.1
0.6
(a)
22.2
0.6
28.6
0.8
31.8
0.9
Pipe Ø (mm)
Minimal thickness t (mm)
34.9
1.0
38.1+41.3
1.1
(a)
If annealed temper grade is 1.
The refrigerant pipes and branches must meet the condition of
design pressure 33 bar (3.3 MPa). If it is NOT possible to confirm
this, use the refrigerant branch as mentioned in this chapter.
Confirm that the pipe thickness complies with the required minimum
thickness.
▪ In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the
following into account:
▪ Select the pipe size nearest to the required size.
▪ Use the suitable adapters for the change-over from inch to mm
pipes (field supply).
▪ The additional refrigerant calculation has to be adjusted as
mentioned in To determine the additional refrigerant amount.
14.1.3
To select refrigerant branch kits
Refrigerant refnets
▪ When using refnet joints at the first branch counted from the
outdoor unit side, choose from the following table in accordance
with the capacity of the outdoor unit (example: refnet joint a).
Outdoor unit capacity type
(HP)
2 pipes
8+10
KHRQ22M29T9
12~22
KHRQ22M64T
24~42
KHRQ22M75T
▪ For refnet joints other than the first branch (example refnet joint b),
select the proper branch kit model based on the total capacity
index of all indoor units connected after the refrigerant branch.
Indoor unit capacity index
2 pipes
<200
KHRQ22M20T
200≤x<290
KHRQ22M29T9
290≤x<640
KHRQ22M64T
≥640
KHRQ22M75T
▪ Concerning refnet headers, choose from the following table in
accordance with the total capacity of all the indoor units connected
below the refnet header.
Indoor unit capacity index
2 pipes
<200
KHRQ22M29H
200≤x<290
290≤x<640
KHRQ22M64H
(a)
≥640
KHRQ22M75H
(a)
If the pipe size above the refnet header is Ø34.9 or more,
KHRQ22M75H is required.
INFORMATION
Maximum 8 branches can be connected to a header.
▪ How to choose an outdoor multi connection piping kit (required if
the outdoor unit capacity is 22 HP or more). Choose from the
following table in accordance with the number of outdoor units.
Number of outdoor units
Branch kit name
2
BHFQ22P1007
3
BHFQ22P1517