Installation
Installation of Outdoor Units
47
parts other than those specified by Daikin are used,
fire or explosion may occur.
CAUTION
•
Do not touch the switch with wet fingers. Touching a
switch with wet fingers can cause electric shock.
•
Do not allow children to play on or around the unit to
prevent injury.
•
Do not touch the refrigerant pipes during and
immediately after operation as the refrigerant pipes
may be hot or cold, depending on the condition of
the refrigerant flowing through the refrigerant
piping, compressor, and other refrigerant cycle
parts. Your hands may suffer burns or frostbite if you
touch the refrigerant pipes. To avoid injury, give the
pipes time to return to normal temperature or, if you
must touch them, be sure to wear proper gloves.
•
Install drain piping to proper drainage. Improper
drain piping may result in water leakage and
property damage.
•
Insulate piping to prevent condensation.
•
Be careful when transporting the product.
•
Do not turn off the power immediately after stopping
operation. Always wait for at least 5 minutes before
turning off the power. Otherwise, water leakage may
occur.
•
Do not use a charging cylinder. Using a charging
cylinder may cause the refrigerant to deteriorate.
•
Refrigerant R-410A in the system must be kept clean,
dry, and tight.
(a) Clean and Dry -- Foreign materials (including
mineral oils such as SUNISO oil or moisture)
should be prevented from getting into the
system.
(b) Tight -- R-410A does not contain any chlorine,
does not destroy the ozone layer, and does not
reduce the earth’s protection again harmful
ultraviolet radiation. R-410A can contribute to
the greenhouse effect if it is released. Therefore
take proper measures to check for the tightness
of the refrigerant piping installation. Read the
chapter
Refrigerant Piping
and follow the
procedures.
•
Since R-410A is a blend, the required additional
refrigerant must be charged in its liquid state. If the
refrigerant is charged in a state of gas, its
composition can change and the system will not
work properly.
•
The indoor unit is for R-410A. See the catalog for
indoor models that can be connected. Normal
operation is not possible when connected to other
units.
•
Remote controller (wireless kit) transmitting
distance can be shorter than expected in rooms with
electronic fluorescent lamps (inverter or rapid start
types). Install the indoor unit far away from
fluorescent lamps as much as possible.
•
Indoor units are for indoor installation only. Outdoor
units can be installed either outdoors or indoors.
This unit is for indoor use.
•
Do not install the air conditioner or heat pump in the
following locations:
(a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen.
Plastic parts may deteriorate and fall off or result in
water leakage.
(b) Where corrosive gas, such as sulfurous acid gas, is
produced.
Corroding copper pipes or soldered parts may
result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation
of the control system and cause the unit to
malfunction.
(d) Where flammable gas may leak, where there is
carbon fiber, or ignitable dust suspension in the air,
or where volatile flammables such as thinner or
gasoline are handled. Operating the unit in such
conditions can cause a fire.
•
Take adequate measures to prevent the outside unit
from being used as a shelter by small animals. Small
animals making contact with electrical parts can
cause malfunctions, smoke, or fire. Instruct the
customer to keep the area around the unit clean.
NOTE
•
Install the power supply and control wires for the
indoor and outdoor units at least 3.5 feet away from
televisions or radios to prevent image interference or
noise. Depending on the radio waves, a distance of 3.5
feet may not be sufficient to eliminate the noise.
•
Dismantling the unit, treatment of the refrigerant, oil
and additional parts must be done in accordance
with the relevant local, state, and national
regulations.
•
Do not use the following tools that are used with
conventional refrigerants: gauge manifold, charge
hose, gas leak detector, reverse flow check valve,
refrigerant charge base, vacuum gauge, or
refrigerant recovery equipment.
•
If the conventional refrigerant and refrigerator oil are
mixed in R-410A, the refrigerant may deteriorate.
•
This air conditioner or heat pump is an appliance
that should not be accessible to the general public.
3P215731-10R
Содержание VRV III REMQ120PBTJ
Страница 1: ...EDUS 391004 N AMERICAS AMERICAS Installation...
Страница 24: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 23 1P218719...
Страница 25: ...REFNET Pipe System EDUS391004 N 24 Installation of Outdoor Units 1P218720...
Страница 26: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 25 1P218720...
Страница 28: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 27 1P280278A...
Страница 29: ...REFNET Pipe System EDUS391004 N 28 Installation of Outdoor Units 1P280278A...
Страница 30: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 29 1P280279...
Страница 33: ...REFNET Pipe System EDUS391004 N 32 Installation of Outdoor Units 1P218714...
Страница 34: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 33 1P218714...
Страница 35: ...REFNET Pipe System EDUS391004 N 34 Installation of Outdoor Units 1P218715...
Страница 36: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 35 1P218715...
Страница 38: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 37 3D071080...
Страница 39: ...REFNET Pipe System EDUS391004 N 38 Installation of Outdoor Units 1P280510A...
Страница 40: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 39 1P280510A...
Страница 41: ...REFNET Pipe System EDUS391004 N 40 Installation of Outdoor Units 1P280511A...
Страница 42: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 41 1P280511A...
Страница 113: ...EDUS391004 N Field Setting Installation of Outdoor Units 113 2P281604A...
Страница 114: ...Field Setting EDUS391004 N 114 Installation of Outdoor Units 2P281604A...
Страница 115: ...EDUS391004 N Field Setting Installation of Outdoor Units 115 2P281604A...
Страница 116: ...Field Setting EDUS391004 N 116 Installation of Outdoor Units 2P281604A...
Страница 117: ...EDUS391004 N Field Setting Installation of Outdoor Units 117 RXYQ72PBYD RXYQ96PBYD RXYQ120PBYD 3P281590...
Страница 121: ...EDUS391004 N Field Setting Installation of Outdoor Units 121 2P281605A...
Страница 122: ...Field Setting EDUS391004 N 122 Installation of Outdoor Units 2P281605A...
Страница 124: ...Field Setting EDUS391004 N 124 Installation of Outdoor Units 2P281605A...
Страница 129: ......