Installation
EDUS391004-N
100
Installation of Outdoor Units
Outdoor unit multi connection piping kit and
Refrigerant branch kit selection
Pipe size selection
•
Refrigerant branch kits can only be used with R410A.
•
When multi outdoor system are installed, be sure to use the
special separately sold Outdoor unit multi connection piping
kit. (BHFP26P90U).
(For how to select the proper kit, follow the table at right.)
•
Never use BHFP26M90U, BHFP22M90U for M type of this
series or T joint (field supplied).
How to select the REFNET joint
Piping between outdoor unit (*2 and refrigerant branch kit (part A)
How to select the REFNET header
When using REFNET joint at the first branch counted from the outdoor unit side,
choose from the following table in accordance with the outdoor unit capacity type.
(Example : REFNET joint A)
Choose from the following table in accordance with the outdoor
units system capacity type.
Piping between outdoor unit multi connection piping kit and outdoor unit (part B)
Choose from the following table in accordance with the capacity type of
the outdoor unit connected.
Choose from the following table in accordance with the total capacity index of all
the indoor units connected below the REFNET header.
How to select the outdoor unit multi connection piping kit
(This is required when the system is multi outdoor unit system.)
Choose from the following table in accordance with the number of outdoor units.
Choose the REFNET joints other than the first branch from the following table in accordance
with the total capacity index of all the indoor units connected below the REFNET joint.
Outdoor unit capacity type
REYQ144~216P type
REYQ240~336P type
Indoor unit total capacity index
X < 72
72
≤
X < 111
111
≤
X < 246
246
≤
X
Refrigerant branch kit name
KHRP25M72TU9
KHRP25M73TU9
3 pipes
KHRP25M22T
KHRP25M33T
KHRP25M72TU9
KHRP25M73TU9
2 pipes
KHRP26M22T
KHRP26M33T
KHRP26M72TU9
KHRP26M73TU9
Refrigerant branch kit name
Indoor unit total capacity index
X < 72
72
≤
X < 111
111
≤
X < 230
230
≤
X
Number of outdoor unit
2 units
3 units
Connecting piping kit name
BHFP26P90U
BHFP26P136U
3 pipes
KHRP25M33H9
KHRP25M72H9
KHRP25M73H9
2 pipes
KHRP26M22H9 or KHRP26M33H9
KHRP26M33H9
KHRP26M72H9
KHRP26M73H9
Refrigerant branch kit name
Example for indoor units
connected downstream
Example REFNET joint C : Indoor units 5 + 6 + 7 + 8
Example REFNET joint B : Indoor units 7 + 8
Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6
Example REFNET header :
Indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
The thickness and material shall be selected in
accordance with local code.
For an outdoor unit installation, make
the settings in accordance with the
following figure.
Outdoor unit
Equalizer pipe
(part C)
Piping between outdoor unit
multi connection piping kit
and outdoor unit (part B)
Piping between outdoor unit multi
connection piping kits
Piping between outdoor unit and
refrigerant branch kit (part A)
Outdoor unit
capacity type
REYQ144P type
REYQ168P type
REYQ192 · 216P type
REYQ240P type
REYQ264~336P type
Piping size (O. D.)
Piping size (O. D.)
Suction gas pipe
φ
1-1/8
φ
1-3/8
HP/LP gas pipe
φ
7/8
φ
1-1/8
Liquid pipe
φ
1/2
φ
5/8
φ
3/4
Outdoor unit
capacity type
REMQ72
·
96P type
REMQ120P type
Suction gas pipe
φ
7/8
φ
1-1/8
HP/LP gas pipe
φ
3/4
Liquid pipe
φ
3/8
φ
1/2
Piping between refrigerant branch kits
Piping between refrigerant branch kit and BS unit
Piping between BS unit and refrigerant branch kit
Choose from the following table in accordance with the total capacity type of all the
indoor units connected downstream.
Piping between refrigerant branch kit, BS unit and indoor unit.
Equalizer pipe (part C)
Match to the size of the connection piping on the indoor unit.
*1 Connection piping must not exceed the refrigerant Piping size between outdoor
unit and refrigerant branch kit (part A)
*2 When selecting 2 pipes line(gas pipe and liquid pipe), use Suction gas pipe
column for gas pipe and Liquid pipe column for liquid pipe.
Indoor capacity index
X < 54
54
≤
X < 72
72
≤
X < 111
111
≤
X < 162
162
≤
X < 230
230
≤
X < 300
300
≤
X
Indoor unit capacity type
07
·
09
·
12
·
18
24
·
30
·
36
·
48
·
54
72
96
gas pipe
φ
1/2
φ
5/8
φ
3/4
φ
7/8
Liquid pipe
φ
1/4
φ
3/8
Piping size (O. D.)
φ
3/4
(unit : in.)
(unit : in.)
Piping size (O. D.)
(unit : in.)
Piping size (O. D.)
(unit : in.)
(unit : in.)
Suction gas pipe
φ
5/8
φ
3/4
φ
7/8
φ
1-1/8
φ
1-3/8
φ
1-5/8
HP/LP gas pipe
φ
1/2
φ
5/8
φ
3/4
φ
1-1/8
Liquid pipe
φ
3/8
φ
1/2
φ
5/8
φ
3/4
C: 3P215731-11R
Содержание VRV III REMQ120PBTJ
Страница 1: ...EDUS 391004 N AMERICAS AMERICAS Installation...
Страница 24: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 23 1P218719...
Страница 25: ...REFNET Pipe System EDUS391004 N 24 Installation of Outdoor Units 1P218720...
Страница 26: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 25 1P218720...
Страница 28: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 27 1P280278A...
Страница 29: ...REFNET Pipe System EDUS391004 N 28 Installation of Outdoor Units 1P280278A...
Страница 30: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 29 1P280279...
Страница 33: ...REFNET Pipe System EDUS391004 N 32 Installation of Outdoor Units 1P218714...
Страница 34: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 33 1P218714...
Страница 35: ...REFNET Pipe System EDUS391004 N 34 Installation of Outdoor Units 1P218715...
Страница 36: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 35 1P218715...
Страница 38: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 37 3D071080...
Страница 39: ...REFNET Pipe System EDUS391004 N 38 Installation of Outdoor Units 1P280510A...
Страница 40: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 39 1P280510A...
Страница 41: ...REFNET Pipe System EDUS391004 N 40 Installation of Outdoor Units 1P280511A...
Страница 42: ...EDUS391004 N REFNET Pipe System Installation of Outdoor Units 41 1P280511A...
Страница 113: ...EDUS391004 N Field Setting Installation of Outdoor Units 113 2P281604A...
Страница 114: ...Field Setting EDUS391004 N 114 Installation of Outdoor Units 2P281604A...
Страница 115: ...EDUS391004 N Field Setting Installation of Outdoor Units 115 2P281604A...
Страница 116: ...Field Setting EDUS391004 N 116 Installation of Outdoor Units 2P281604A...
Страница 117: ...EDUS391004 N Field Setting Installation of Outdoor Units 117 RXYQ72PBYD RXYQ96PBYD RXYQ120PBYD 3P281590...
Страница 121: ...EDUS391004 N Field Setting Installation of Outdoor Units 121 2P281605A...
Страница 122: ...Field Setting EDUS391004 N 122 Installation of Outdoor Units 2P281605A...
Страница 124: ...Field Setting EDUS391004 N 124 Installation of Outdoor Units 2P281605A...
Страница 129: ......