2 Specific installer safety instructions

Installation and operation manual

6

RXYSA4~6A7V/Y1B

VRV 5-S system air conditioner

4P600329-1E – 2023.02

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

NOTICE

NEVER  install  a  drier  to  this  unit  to  guarantee  its  lifetime.
The drying material may dissolve and damage the system.

Charging refrigerant (see 

"15 Charging refrigerant"

 [

4

 28])

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

WARNING

Charging  of  refrigerant  MUST  be  in  accordance  with  the
instructions  from  this  manual.  See 

"15  Charging

refrigerant"

 [

4

 28].

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

Electrical installation (see 

"16 Electrical installation"

 [

4

 30])

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
national wiring regulation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

Electrical  wiring  connection  method  MUST  be  in
accordance  with  the  instructions  from  this  manual.  See

"16 Electrical installation"

 [

4

 30].

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  extension  cords,  or

connections  from  a  star  system.  They  can  cause
overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

CAUTION

Do NOT push or place redundant cable length into the unit.

Commissioning (see 

"19 Commissioning"

 [

4

 37])

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When  performing  the  test  operation,  NOT  ONLY  the
outdoor unit, but the connected indoor unit will operate as
well.  Working  on  an  indoor  unit  while  performing  a  test
operation is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

Troubleshooting (see 

"20 Troubleshooting"

 [

4

 39])

WARNING

▪ When  carrying  out  an  inspection  on  the  switch  box  of

the  unit,  ALWAYS  make  sure  that  the  unit  is
disconnected  from  the  mains.  Turn  off  the  respective
circuit breaker.

▪ When a safety device was activated, stop the unit and

find  out  why  the  safety  device  was  activated  before
resetting  it.  NEVER  shunt  safety  devices  or  change
their  values  to  a  value  other  than  the  factory  default
setting.  If  you  are  unable  to  find  the  cause  of  the
problem, call your dealer.

WARNING

Prevent hazards due to inadvertent resetting of the thermal
cut-out:  power  to  this  appliance  MUST  NOT  be  supplied
through  an  external  switching  device,  such  as  a  timer,  or
connected to a circuit that is regularly turned ON and OFF
by the utility.

2.1

Instructions for equipment using
R32 refrigerant

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Содержание VRV 5-S RXYSA4A7V1B

Страница 1: ...llation and operation manual VRV 5 S system air conditioner English Installation and operation manual VRV 5 S system air conditioner RXYSA4A7V1B RXYSA5A7V1B RXYSA6A7V1B RXYSA4A7Y1B RXYSA5A7Y1B RXYSA6A...

Страница 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Страница 3: ...1 0 21 5 22 0 22 6 23 1 23 6 24 2 24 7 25 3 25 8 26 3 26 9 27 4 27 9 4 6 5 5 6 0 6 5 6 9 7 2 7 6 7 9 8 2 8 6 9 2 9 8 10 4 11 1 11 7 12 3 12 9 13 5 14 1 14 7 15 4 16 0 16 6 17 2 17 8 18 4 19 0 19 6 20...

Страница 4: ...urs 15 8 2 14 Symptom The outdoor unit fan does not spin 16 8 2 15 Symptom The compressor in the outdoor unit does not stop after a short heating operation 16 8 2 16 Symptom The inside of an outdoor u...

Страница 5: ...data Detailed step by step instructions and background information for basic and advanced usage Format Digital files on https www daikin eu Use the search function to find your model Latest revisions...

Страница 6: ...WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete ea...

Страница 7: ...d excessive vibration or pulsation to refrigeration piping Protect the protection devices piping and fittings as much as possible against adverse environmental effects Provide space for expansion and...

Страница 8: ...vironment and human health 3 2 Instructions for safe operation CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appli...

Страница 9: ...ON NEVER expose little children plants or animals directly to the airflow WARNING The unit is equipped with a refrigerant leak detection system for safety To be effective the unit MUST be electrically...

Страница 10: ...r interface whose display shows change over under centralised control refer to installation and operation manual of the user interface When the display change over under centralised control flashes re...

Страница 11: ...to operation if the room temperature is low 20 C 6 3 2 To use the dry program WITHOUT cool heat changeover remote control switch To start 1 Press the operation mode selector button on the user interfa...

Страница 12: ...the master user interface can select heating or cooling mode 6 5 2 To designate the master user interface 1 Press the operation mode selector button of the current master user interface for 4 seconds...

Страница 13: ...l name of the unit The manufacturing number stated on the nameplate of the unit The installation date The symptoms or malfunction and details of the defect WARNING Do NOT modify disassemble remove rei...

Страница 14: ...mistor malfunction indoor gas Suction air thermistor malfunction indoor Discharge air thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor R32 sensor malfunct...

Страница 15: ...g cooling operation If the interior of an indoor unit is extremely contaminated the temperature distribution inside a room becomes uneven It is necessary to clean the interior of the indoor unit Ask y...

Страница 16: ...es hydrofluorocarbon Contact your dealer when discarding this unit It is required by law to collect transport and discard the refrigerant in accordance with the hydrofluorocarbon collection and destru...

Страница 17: ...ected failure or disconnection of the R32 sensor located in the indoor unit For more information about the SVS output see 16 4 To connect the external outputs 432 Indoor unit installation NOTICE If on...

Страница 18: ...t of the remote controller is not sufficient to guarantee the 15 dB difference This alarm can be connected to the SVS output channel of the outdoor unit or to the optional output PCB of the indoor uni...

Страница 19: ...6 a b b d a b b b d Group control is allowed up to a maximum of 5 indoor units connected to different ports or connected to the same port At least one R32 safety system compatible remote controller s...

Страница 20: ...Lowest underground floor Lowest underground floor c Effective installation height Effective installation height Determine the value for both the lowest underground floor AND the other floors The tota...

Страница 21: ...System charge kg 16 0 Judgement a b b b b B D C A a Outdoor unit b Indoor unit A B C D Room A B C D Example 2 Room A B C D Area m 10 20 10 20 Installation height m 3 0 2 2 3 0 2 2 Lowest underground f...

Страница 22: ...allation site WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater 13 1 1 Inst...

Страница 23: ...nit 13 3 1 To provide the installation structure Prepare 4 sets of anchor bolts nuts and washers field supply as follows mm 7 5 8 150 4 8 0 4 9 0 4 8 5 4 M12 a a Make sure not to cover the drain holes...

Страница 24: ...cated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the pa...

Страница 25: ...or unit Use the same diameters as the connections liquid gas on the indoor units The diameters of the indoor units are as follows Indoor unit capacity index Piping outer diameter size mm Gas pipe Liqu...

Страница 26: ...panel Especially for the bottom and side connection be sure to protect the piping with suitable insulation to prevent it from coming into contact with the casing 1 Do the following Remove the service...

Страница 27: ...es either horizontally or vertically Mount the refnet header so that it branches horizontally A B 3 0 a b c d a a Horizontal surface b Refnet joint mounted vertically c Refnet joint mounted horizontal...

Страница 28: ...order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed within 12 minutes after the indoor and outdoor units are powered on the compressor w...

Страница 29: ...ng If Then The determined additional refrigerant amount is reached Disconnect the manifold from the liquid line You do not have to perform the Charging refrigerant in manual additional refrigerant cha...

Страница 30: ...Potential NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantit...

Страница 31: ...ice 30 mA MUST comply with national wiring regulation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of combination with indoor units for exact values 16 3 To conn...

Страница 32: ...sh c Nut d Frame e Tube 8 Route the cables out of the unit WARNING Avoid sharp edges when routing cables to the rear Make sure to route the cables through the left side of the accumulator foot when pa...

Страница 33: ...75 mm For the SVEO connection it is recommended to use a shielded cable The cable shield must be earthed at the marked earthing point that is located on the support frame of the terminal Y1 V1 c a b c...

Страница 34: ...ich can withstand a temperature of 120 C for gas piping Reinforce the insulation on the refrigerant piping according to the installation environment Ambient temperature Humidity Minimum thickness 30 C...

Страница 35: ...ue and changing the current field setting value is possible In general normal operation can be resumed without special intervention after changing field settings Some field settings are used for speci...

Страница 36: ...on Access Action Mode 1 Push BS1 one time 7 segment display indication changes to Push BS1 one more time to return to the default situation Mode 2 Push BS1 for at least 5 seconds 7 segment display ind...

Страница 37: ...Note For an ESP level higher than 45 Pa level 0 is kept for reliability of the fan motor 2 18 Description 0 default Auto setting at commissioning mode and stand by mode 1 Auto setting at commissioning...

Страница 38: ...ox and the inside of the unit for loose connections or damaged electrical components Pipe size and pipe insulation Be sure that correct pipe sizes are installed and that the insulation work is properl...

Страница 39: ...rmality When the test operation is fully completed normal operation will be possible after 5 minutes 19 6 Correcting after abnormal completion of the test run The test operation is only completed if t...

Страница 40: ...ring any excessive refrigerant with a refrigerant recovery machine Ambient temperature sensor malfunction R1T A1P X18A Check connection on PCB or actuator Discharge temperature sensor malfunction R21T...

Страница 41: ...ce manual for more information WARNING The unit is equipped with a refrigerant leak detection system for safety To be effective the unit MUST be electrically powered at all times after installation ex...

Страница 42: ...nimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and...

Страница 43: ...ributor Refrigerant flow l Heat exchanger Cooling m Accumulator Heating n Muffler o Capillary tube p Compressor accumulator M1C Compressor M1F Fan motor HPS A High pressure switch automatic reset HPS...