18 Configuration
Installation and operation manual
35
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600329-1E – 2023.02
18
Configuration
DANGER: RISK OF ELECTROCUTION
INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
18.1
Making field settings
18.1.1
About making field settings
To configure the heat pump system, you must give input to the
outdoor unit's main PCB (A1P). This involves the following field
setting components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
▪ DIP switches (only change the factory settings if you install a cool/
heat selector switch).
See also:
▪
"18.1.3 Field setting components"
▪
"18.1.2 To access the field setting components"
PC configurator
V
Y
a
b
c (X27A)
A1P
A1P
b
c (X27A)
a
2
3
4
5
H J
ST
X27A
a
PC
b
Cable (EKPCCAB*)
c
Extension cable connected to X27A
X27A
Connector
A1P
Outdoor unit main PCB
Mode 1 and 2
Mode
Description
Mode 1
(monitoring
settings)
Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
contents can be monitored as well.
Mode
Description
Mode 2
(field settings)
Mode 2 is used to change the field settings of
the system. Consulting the current field setting
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation (e.g., one time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
See also:
▪
"18.1.4 To access mode 1 or 2"
▪
▪
▪
"18.1.7 Mode 1: monitoring settings"
▪
"18.1.8 Mode 2: field settings"
18.1.2
To access the field setting components
See
"13.2.1 To open the outdoor unit"
23].
18.1.3
Field setting components
Location of the 7‑segment displays, buttons and DIP switches:
a
b
BS1 BS2
DS2 DS1
BS3
c
18‒1 1 Phase (V)
a
b
BS1 BS2
DS1 DS2
BS3
c
18‒2 3 Phase (Y)
BS1
MODE: For changing the set mode
BS2
SET: For field setting
BS3
RETURN: For field setting
DS1, DS2
DIP switches
a
7‑segment displays
b
Push buttons
c
DIP switches
DIP switches
Only change the factory settings if you install a cool/heat selector
switch.
DS1‑1
COOL/HEAT selector (refer to the manual of the
cool/heat selector switch).
ON= COOL/HEAT selector active; OFF=not
installed=factory setting
DS1‑2
NOT USED. DO NOT CHANGE THE FACTORY
SETTING.
Push buttons
Use the push buttons to make the field settings. Operate the push
buttons with an insulated stick (such as a closed ball-point pen) to
avoid touching live parts.