27 Technical data
▪
A
subset
of the latest technical data is available on the regional Daikin website
(publicly accessible).
▪
The
full set
of the latest technical data is available on the Daikin Business Portal
(authentication required).
In this chapter
27.1 Service space: Outdoor unit
Make sure the space around the unit is adequate for servicing and the minimum
space for air inlet and air outlet is available (refer to the figure below and choose
one of the possibilities).
a
b
a
c
d
a
b
a
e
d
e
c
a
b
a
e
d
f
c
a
b
a
e
b
d
c
a
b
a
e
d
f
c
1
2
3
4
5
Layout
A+B+C+D
A+B
Possibility 1
Possibility 2
1
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
a≥200 mm
b≥300 mm
2
a≥10 mm
b≥300 mm
c≥10 mm
d≥500 mm
e≥20 mm
a≥50 mm
b≥100 mm
c≥50 mm
d≥500 mm
e≥100 mm
a≥200 mm
b≥300 mm
e≥400 mm