2 Specific installer safety instructions

Installation and operation manual

7

BS4~12A14AJV1B
VRV 5 branch selector unit
4P670163-1 – 2022.02

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

NOTICE

▪ Do NOT use mineral oil on flared part.

▪ Do NOT reuse piping from previous installations.

▪ NEVER  install  a  drier  to  this  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

Electrical installation (see 

"15 Electrical installation"

 [

4

 31])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF ELECTROCUTION

Before performing work on the unit, be sure to disconnect
any power source connected to the unit.

WARNING

Electrical  wiring  connection  method  MUST  be  in
accordance  with  the  instructions  from  this  manual.  See

"15 Electrical installation"

 [

4

 31].

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables do NOT come into contact with sharp edges or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST
be replaced by the manufacturer, its
service agent or similarly qualified
persons in order to avoid a hazard.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

Appliance  MUST  be  installed  in  accordance  with  national
wiring regulations.

CAUTION

Do NOT push or place redundant cable length in the unit.

CAUTION

Be careful NOT to pinch cables between the service cover
and the switch box.

Commissioning (see 

"17 Commissioning"

 [

4

 38])

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When  performing  the  test  operation,  NOT  ONLY  the
outdoor unit, but the connected indoor unit will operate as
well.  Working  on  an  indoor  unit  while  performing  a  test
operation is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet (damper).

Troubleshooting (see 

"19 Troubleshooting"

 [

4

 41])

DANGER: RISK OF BURNING/SCALDING

WARNING

Prevent hazards due to inadvertent resetting of the thermal
cut-out:  power  to  this  appliance  MUST  NOT  be  supplied
through  an  external  switching  device,  such  as  a  timer,  or
connected to a circuit that is regularly turned ON and OFF
by the utility.

WARNING

▪ When  carrying  out  an  inspection  on  the  switch  box  of

the  unit,  ALWAYS  make  sure  that  the  unit  is
disconnected  from  the  mains.  Turn  off  the  respective
circuit breaker.

▪ When a safety device was activated, stop the unit and

find  out  why  the  safety  device  was  activated  before
resetting  it.  NEVER  shunt  safety  devices  or  change
their  values  to  a  value  other  than  the  factory  default
setting.  If  you  are  unable  to  find  the  cause  of  the
problem, call your dealer.

2.1

Instructions for equipment using
R32 refrigerant

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

Содержание VRV 5 BS4A14AJV1B

Страница 1: ...Installation and operation manual VRV 5 branch selector unit English Installation and operation manual VRV 5 branch selector unit BS4A14AJV1B BS6A14AJV1B BS8A14AJV1B BS10A14AJV1B BS12A14AJV1B...

Страница 2: ...measure c External alarm d m kg Amin m All other floors a All other floors a Lowest under ground floor b No safety measure c No safety measure c External alarm d 5 16 15 16 35 207 104 207 6 23 18 23...

Страница 3: ...iai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo pred...

Страница 4: ...he products are used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the...

Страница 5: ...3 4 3 To install the drain piping 24 13 5 Installing the ventilation ducting 24 13 5 1 To install the ducting field supply 24 13 5 2 To install the duct closing plate 25 13 5 3 To switch the air in an...

Страница 6: ...approved by the manufacturer are used in the duct work WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct wor...

Страница 7: ...wer supply cables WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Use an all pole disc...

Страница 8: ...enance purposes See 12 3 To determine the required safety measures 4 14 to check if your system meets the R32 safety requirements For the user 3 User safety instructions Always observe the following s...

Страница 9: ...ways have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation WARNING This unit contains electrical and hot parts WARNING Before oper...

Страница 10: ...structions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable...

Страница 11: ...the unit by yourself Ask a qualified service person to perform this work 6 1 Precautions for maintenance and service CAUTION See 3 User safety instructions 48 to acknowledge all related safety instruc...

Страница 12: ...ned malfunctions is evident investigate the system in accordance with the following procedures Malfunction Measure If a refrigerant leak occurs error code Actions will be taken by the system Do NOT tu...

Страница 13: ...it and options 11 1 About combining units and options 11 1 1 Possible options for the BS unit INFORMATION All possible options are mentioned in the option list below For more information about an opti...

Страница 14: ...he outdoor unit For installation of the indoor unit see the installation and operation manual delivered with the indoor unit For compatibility of indoor units see the latest version of the technical d...

Страница 15: ...arm e Ventilated enclosure Ventilated enclosure Use the total amount of refrigerant in the system and the area of the room in which the BS unit is installed to check what is the safety measure that ne...

Страница 16: ...ntrolled number of people are present accessible for persons not familiar with the necessary safety precautions To warn at a supervised location connect a supervisor remote controller to the system Th...

Страница 17: ...hen compared with the pressure of the surroundings The minimum required airflow rate AFROUT is 18 8 m h and the pressure drop generated by the BS unit should lead to a pressure inside the BS unit Pint...

Страница 18: ...parallel BS units are connected to a single extraction fan Each BS unit benefits from a direct airflow path to the extraction fan In case of a refrigerant leak in any BS unit the damper of that BS uni...

Страница 19: ...t run that simulates a refrigerant leak See 17 1 BS unit test run 438 for more details Field settings Multiple BS units in series one extraction fan Code Description Value 2 0 Cluster indication 1 ena...

Страница 20: ...ames an operating gas appliance or an operating electric heater 13 1 1 Installation site requirements of the unit CAUTION Appliance NOT accessible to the general public install it in a secured area pr...

Страница 21: ...length Keep drain piping as short as possible Drain pipe size Keep the pipe size equal to or greater than that of the connecting pipe vinyl pipe of 20 mm nominal diameter and 26 mm outer diameter Bad...

Страница 22: ...lt flow Ducting on both sides B Reversed flow Only ducting on the air outlet side B Reversed flow Ducting on both sides C No extraction ventilation installed 1 To extraction fan or another BS unit 2 F...

Страница 23: ...pension bolt Leave enough space for maneuvering with the unit between the nut and double nut 3 Position the unit by hooking the hanger brackets of the unit around the suspension bolts in between the t...

Страница 24: ...n hose Note Start on the screw part of the metal clamp work your way around the clamp and end overlapping your starting point 5 b a c d a Drain pipe connection attached to the unit b Drain hose access...

Страница 25: ...der the field supply insulation Create an overlap of 50 mm If the entire outlet duct is thermally insulated from the unit to the outside wall the accessory sealing material is not necessary a d e d e...

Страница 26: ...wire Store the screw in a safe place Cut the cable ties that fix the damper wire to the pipe and the one that bundles the damper wire a b b b a Damper wire b Cable ties 8 Remove the damper Remove the...

Страница 27: ...his makes the connection airtight Attach the damper with 4 screws 4 PH2 SW8 3 2 N m a b b b b c 1 2 a Damper wire b Screw c Damper 15 Connect the damper wires a b c 1 PH2 1 7 N m a Connector b Earth w...

Страница 28: ...a b c d BS4A a b b c d BS6 12A a Damper wire b Tie wrap to fix damper wire to piping field supply c Tie wrap to bundle the damper wire field supply d Leftmost wire fixing plate To re install the switc...

Страница 29: ...6 Maximum number of indoor units connected to BS units in refrigerant flow through c 64 14 2 Preparing refrigerant piping 14 2 1 Refrigerant piping requirements NOTICE The piping and other pressure co...

Страница 30: ...erant flow through with another BS unit and unused branch pipes when no indoor unit is connected to that branch pipe port 5 In case of stopper pipes install stopper pipe insulation tubes accessory Add...

Страница 31: ...art from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at l...

Страница 32: ...e corresponding indoor unit multiple indoor units connected to the same branch the terminals F1 F2 Indoor unit X on the BS unit to the F1 F2 terminals on the first indoor unit Connect the F1 F2 termin...

Страница 33: ...tape e Transmission wiring F1 F2 f Insulation 15 4 To set the DIP switches The DIP switches are located on the PCB s A1P A2P BS6 12A and A3P BS10 12A A1P A2P A3P A B C D E F G H I J K L A B C D E F G...

Страница 34: ...MPLE a FAN output terminal b Relay c Extraction fan power supply d Extraction fan SVS output external alarm The SVS output is a potential free contact on terminal X6M that closes in case a leak is det...

Страница 35: ...Value Example Description Default situation Mode 1 Mode 2 Description Setting 8 in mode 2 Value 4 in mode 2 16 1 4 To access mode 1 or 2 Initialisation default situation NOTICE Be sure to turn ON the...

Страница 36: ...r more than 5 seconds Result Mode 2 is accessed 3 Push BS2 seven times Result Mode 2 setting 7 is addressed 4 Push BS3 1 time the value which is returned depending on the actual field situation is the...

Страница 37: ...on the 7 segment display of the outdoor unit This setting must only be made on the leftmost main PCB A1P of each BS unit 2 6 Commissioning check 0 default Incomplete 1 Completed 2 7 Setting to enable...

Страница 38: ...he BS unit test run The BS unit test run has to be performed on all BS units in the system before the test run of the outdoor unit The BS unit test run has to confirm that the required safety measures...

Страница 39: ...e airflow rate at the air inlet damper of the BS unit Tip Use the duct connection kit EKBSDCK and an anemometer with a funnel to conduct the entire airflow through the anemometer Postrequisite Remove...

Страница 40: ...uring BS unit test run Symptom The damper does not open Possible causes Corrective action Incorrect field settings Check if all field settings are made correctly When in parallel or series configurati...

Страница 41: ...by your local dealer This chapter gives you an overview of the most possible error codes and their descriptions as they appear on the user interface INFORMATION See the service manual for The complet...

Страница 42: ...PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Symbol Meaning Q M Thermo switch Q R Residual current device R R...

Страница 43: ...or for the product Authorised installer Technical skilled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All...

Страница 44: ...4P670163 1 2022 02 Copyright 2022 Daikin 4P670163 1 0000000L Verantwortung f r Energie und Umwelt...

Отзывы: