• Indoor Units • CONCEALED CEILING UNIT • FXMQ-PVE
1
Specifications
1-2 ELECTRICAL SPECIFICATIONS
FXMQ40PVE
FXMQ50PVE
FXMQ63PVE
FXMQ80PVE
FXMQ100PVE
FXMQ125PVE
Power Supply
Name
VE
Phase
1~
Frequency
Hz
50/60
Voltage
V
220-240/220
Current
Minimum circuit amps
(MCA)
A
1.4
1.6
1.8
2.3
2.9
3.4
Maximum fuse amps (MFA) A
16
16
16
16
16
16
Full load amps (FLA)
A
1.1
1.3
1.4
1.8
2.3
2.7
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker