Si71-812
Inspection and Maintenance of the Humidifier
Maintenance
43
2.2
Replacing the Humidifier Element
Replacing the
Humidifier
Element
<VKM-GAMV1
series only>
The humidifier element needs to be replaced regularly.
The humidifier element should in general be replaced once every three years when supply
water is soft water, but outside factors (water quality, hard water, etc.) as well as operating
conditions (24-hour-a-day air conditioning, etc.) may shorten its productive life.
Contact your dealer if you have any questions.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of
hardness : 150mg/l.
(Life of humidifying element is about 1 year (1,500 hours), under the supply water conditions of
hardness : 400mg/l.)
Annual operating hours : 10 hours/day × 26 days / month × 5 month = 1,300 hours.
Contact your dealer for details.
Note : Breakage due to taking apart or cleaning inside by anyone other than our authorized
dealers may not be included in the warranty.
Содержание VKM50GAV1
Страница 9: ...Introduction Si71 812 viii...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2...
Страница 43: ...Operation Si71 812 34 Operation...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1...
Страница 103: ...Piping Diagram Si71 812 94 Appendix...
Страница 105: ...Si71 812 ii Index...