Troubleshooting
Si71-812
62
Troubleshooting
2.7
“
A1
”
Indoor Unit: PC Board Defect
Remote
Controller
Display
A1
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Check data from E²PROM.
Malfunction
Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.
Supposed
Causes
Defect of indoor unit PC board (A2P)
Troubleshooting
Turn power supply OFF, then
power ON again.
Does
the system return
to normal?
YES
External factor other than
malfunction (for example,
noise etc.).
Replace the indoor unit PC
board (A2P).
(V2777)
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание VKM50GAV1
Страница 9: ...Introduction Si71 812 viii...
Страница 10: ...Si71 812 General Constructions 1 Part 1 General Constructions 1 General Information 2 1 1 Features 2...
Страница 43: ...Operation Si71 812 34 Operation...
Страница 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance...
Страница 91: ...Troubleshooting Si71 812 82 Troubleshooting...
Страница 92: ...Si71 812 Field Setting 83 Part 7 Field Setting 1 Field Setting 84 1 1 Field Setting and Test Run 84...
Страница 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1...
Страница 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1...
Страница 103: ...Piping Diagram Si71 812 94 Appendix...
Страница 105: ...Si71 812 ii Index...