8 Configuration
Installer and user reference guide
28
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1 – 2017.08
8.3
Settings for all configurations
Setting 17(27)-4: First choose the fan speed. Set it to high or ultra-
high.
Direct duct connection
or external fan
All other system configurations
2000
Choose between 19(29)-0-04 or 19(29)-0-05
Warning: The ducting
pressure drop of the top
and bottom units has to be
equal to have a balanced
system.
VAM350~1000
Setting 19(29)-2 and setting
19(29)-3: Balance return air
and outdoor air with fan steps
1-15, based on the air flow
curves (see the databook) and
the system pressure drop.
Setting 19(29)-2 and setting
19(29)-3: Balance return air
and outdoor air with fan steps
1-15, based on the air flow
curves (see the databook) and
the system pressure drop.
You MUST activate setting
19(29)-0-03.
Warning: If it is NOT activated,
the clean filter signal will NOT
be given at the correct time.
You can activate setting
19(29)-0-04.
Warning: If it is NOT activated,
the clean filter signal will NOT
be given at the correct time.
You can activate setting
19(29)-0-05: the nominal
point is automatically
determined at the nominal
flow rate (see the databook
for specific values).
8.3.1
About setting 19(29)-0-04 and 19(29)-0-05
▪ When you have configured setting 19(29)‑0‑04 successfully, the
system automatically changes it to setting 19(29)‑0‑01.
▪ When you have configured setting 19(29)‑0‑05 successfully, the
system automatically changes it to setting 19(29)‑0‑02.