8 Configuration
Installer and user reference guide
27
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1 – 2017.08
INFORMATION
▪
Factory settings are marked with grey backgrounds.
▪
(*) See the technical data book for pressure drop curves and selection of fan curves (step 1 to 15).
▪
(**) This setting CANNOT be done with BRC301B61.
▪
The setting modes are mentioned as group settings. Between parentheses are the setting modes for individual unit control.
▪
Group number setting for centralised controller
Mode No. 00: Group controller
Mode No. 30: Individual controller
Regarding the setting procedure, see the section "Group number setting for centralised control" in the operating manual of either the on/off controller or the central controller.
Example
To adjust the auto restart setting to 'on' in the group setting mode, enter mode No. "18", setting switch No. "2" and position No. "02".