13 Configuration
Installation and operation manual
22
VAM350~2000J8VEB
Heat reclaim ventilation unit
4P664011-1 – 2021.08
13.3
Settings for all configurations
Setting 17(27)-4: First choose the fan speed. Set it to high or ultra-high.
Flow "All other system configurations" is not applicable when combining VAM with EKVDX. Check the field settings for both units to make sure
the combination of VAM and EKVDX is operational
Direct duct connection
or external fan
All other system configurations
Models 1500+2000
Choose between 19(29)-0-04 and 19(29)-0-05
Warning: The ducting
pressure drop of the top
and bottom units must be
equal in order to have a
balanced system.
Models 350~1000
Settings 19(29)-2 and
19(29)-3: Balance exhaust air
and supply air with fan steps
1-15, based on the air flow
curves (see the databook) and
the system pressure drop.
Settings 19(29)-2 and
19(29)-3: Balance exhaust air
and supply air with fan steps
1-15, based on the air flow
curves (see the databook) and
the system pressure drop.
You MUST activate setting
19(29)-0-03.
Warning: If this setting is NOT
activated, the clean filter signal
will NOT be given at the
correct time.
You can activate setting
19(29)-0-04.
Warning: If this setting is NOT
activated, the clean filter signal
will NOT be given at the
correct time.
You can activate setting
19(29)-0-05: the nominal
point is automatically
determined at the nominal
flow rate (see the databook
for specific values).