Once the unit has been located, set the unit in place and level
with a spirit level. When spring-type isolators are required,
install springs running under the main unit supports.
The unit should be set initially on shims or blocks at the listed
spring free height. When all piping, wiring, flushing, charging,
etc., is completed, the springs are adjusted upward to loosen
the blocks or shims that are then removed. Refer to
Table 12
on page 24
for correct lifting and mounting locations.
Installation of spring isolators requires flexible piping
connections and at least three feet of flexible electrical conduit
to avoid straining the piping and transmitting vibration and
noise.
A rubber anti-skid pad should be used under isolators if hold-
down bolts are not used.