I
nsTallaTIon
www.DaikinApplied.com 13
IM 1137-4 • TEMPLIFIER
®
MODEL TGZ
CAUTION
Do not use automotive grade antifreeze. Industrial grade
glycols must be used. Automotive antifreeze contains
inhibitors which will cause plating on the copper within the
unit evaporator. The type and handling of glycol used must be
consistent with local codes.
Condenser Water Piping
Arrange the condenser water so the water enters the bottom
connection of the condenser. The condenser water will
discharge the condenser from the top connection. Failing to
arrange the condenser water as stated above will negatively
affect the capacity and efficiency. Note that the condensers are
shipped as either two-pass (10 to 15-degree F Delta-T) or four-
pass (15 to 40-degree F Delta-T). For 2-pass, the connections
are on the vertical centerline of the condenser. For 4-pass, they
are off to one side.
Pressure gauges should be installed in the inlet and outlet
water lines to the condenser. Pressure drop through the
condenser should be measured to determine gpm (L/s)
from pressure drop curves starting on
page 16
. Vibration
eliminators are recommended in both the supply and return
water lines.
Templifier hot water systems usually have a supplementary
heater located after (downstream) of the Templifier condenser
to either boost the hot water temperature or to function as a
standby heater.
Care should be exercised to avoid overly warm water coming
back to the Templifier from the system and causing a relief
valve discharge. This is true whether the unit is running or off.
Maximum temperature is 160°F.
Some jurisdictions require double heat exchange walls
between refrigerant and potable water. Potable water run
directly through a condenser has only one heat exchange wall
(the condenser tube), and certain jurisdictions may require an
intermediate heat exchanger.
Refrigerant Relief Valve Piping
Relief valves are located in the following location and require
piping per code, usually to the outside of the building. All valve
connections are 5/8-inch flare. There is:
• One relief valve in the suction piping of each of two
circuits
• One relief valve on the shell of each of two condenser
circuits
• One additional valve in the discharge piping of circuits
with 30 HP compressors
Table 7: Relief Valve Piping
The current ANSI/ASHRAE Standard 15 specifies that
pressure relief valves on vessels containing Group 1 refrigerant
(R-134a) “shall discharge to the atmosphere at a location not
less than 15 feet (4.6 meters) above the adjoining ground
level and not less than 20 feet (6.1 meters) from any window,
ventilation opening or exit in any building.” The piping must
be provided with a rain cap at the outside terminating point
and a drain at the low point on the vent piping to prevent
water buildup on the atmospheric side of the relief valve. In
addition, a flexible pipe section should be installed in the line to
eliminate any piping stress on the relief valve(s).
The size of the discharge pipe from the pressure relief valve
shall not be less than the size of the pressure relief outlet.
When two or more vessels are piped together, the common
header and piping to the atmosphere shall not be less than
the sum of the area of the relief valve outlets connected to the
header. Fittings should be provided to permit vent piping to be
easily disconnected for inspection or replacement of the relief
valve.
NOTE:
Provide adequate fittings in piping to permit repair or
replacement of relief valve.
TGZ Model Size
Suction Line
Total
Cond. Shell
Total
30 HP Disch.
Line Total
Total per
Unit
040B, 050B, 060B,
080B, 100B, 150B
2
2
0
4
110B, 170B
2
2
1
5
120B, 190B
2
2
2
6