Si12-308
Troubleshooting
Service Diagnosis
173
5.3
Indoor Unit PCB Abnormality
Remote
Controller
Display
A1
Method of
Malfunction
Detection
Evaluation of zero-cross detection of power supply by indoor unit.
Malfunction
Decision
Conditions
When there is no zero-cross detection in approximately 10 continuous seconds.
Supposed
Causes
Faulty indoor unit PCB
Faulty connector connection
Troubleshooting
Note:
Connector Nos. vary depending on models.
Control connector
Connector connection check
(note).
YES
Is it normal?
NO
Correct connections.
Replace PCBs.
(R1400)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Model Type
Connector No.
Wall Mounted Type 25 / 35 class
Terminal strip~Control PCB
Wall Mounted Type 50 / 60 / 71 class Terminal strip~Control PCB
Ceiling Embedded Duct Type
Terminal strip~Control PCB
Floor / Ceiling Suspended Dual Type S37
Floor Standing Type
Control PCB : S7, S201, S203
Power Supply PCB : S8, S202, S204
Содержание Super Multi NX B series
Страница 7: ...Si12 308 vi Table of Contents ...
Страница 29: ...List of Functions Si12 308 18 List of Functions ...
Страница 71: ...Specifications Si12 308 60 Specifications ...
Страница 133: ...Instruction Si12 308 122 System Configuration CDK X 25 35 50 60 A Names of parts Indoor Unit 1 3 4 5 6 8 9 10 7 2 ...
Страница 175: ...Instruction Si12 308 164 System Configuration ...
Страница 227: ...Check Si12 308 216 Service Diagnosis ...
Страница 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Страница 299: ...Si12 308 iv Index ...