Si12-308
Function of Main Structural Parts
Function and Control
91
D Indoor Heat
Exchanger
Thermistor
(DCN)
1. An indoor heat exchanger thermistor is used for controlling target discharge pipe
temperature.
Set a target discharge pipe temperature according to the outdoor and indoor heat exchanger
temperature.
Control the electronic expansion valve opening so that the target discharge pipe
temperature can be obtained.
2. An indoor heat exchanger thermistor is used to prevent freezing.
During the cooling operation, if the temperature drops abnormally, the operating frequency
becomes lower, then the operation must be halted.
3. An indoor heat exchanger thermistor is used for anti-icing control.
During the cooling operation, if the heat exchanger temperature in the room where operation
is halted becomes -1°C, or if the room temperature - heat exchanger in the room where
operation is halted becomes
≥
10°C, it is assumed as icing.
4. An indoor heat exchanger thermistor is used for detecting incorrect wiring.
During the operation of checking incorrect wiring, refrigerant is passed in order from the port
A to detect a heat exchanger temperature, and then wiring and piping will be checked.
Содержание Super Multi NX B series
Страница 7: ...Si12 308 vi Table of Contents ...
Страница 29: ...List of Functions Si12 308 18 List of Functions ...
Страница 71: ...Specifications Si12 308 60 Specifications ...
Страница 133: ...Instruction Si12 308 122 System Configuration CDK X 25 35 50 60 A Names of parts Indoor Unit 1 3 4 5 6 8 9 10 7 2 ...
Страница 175: ...Instruction Si12 308 164 System Configuration ...
Страница 227: ...Check Si12 308 216 Service Diagnosis ...
Страница 288: ...Si12 308 Wiring Diagrams Appendix 277 FTXD50BVMC FTXD60 71BVMC ...
Страница 299: ...Si12 308 iv Index ...