Components
Service manual
78
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
2.9 Intelligent thermal sensor
2.9.1 Checking procedures
1
As there is no specific check procedure for this component, first perform a
check of the indoor unit PCB to check if the intelligent thermal sensor needs
to be replaced. See
After complete check of the indoor unit
PCB, is the problem solved?
Action
Yes
No further actions required.
No
Replace the intelligent thermal sensor,
see
78].
2.9.2 Repair procedures
To remove the intelligent thermal sensor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Disconnect the intelligent thermal sensor connector from the indoor unit PCB.
2
Carefully click the complete intelligent thermal sensor assembly out of the
indoor unit.
a
a
Intelligent thermal sensor assembly
3
To install the intelligent thermal sensor assembly, see
78].
To install the intelligent thermal sensor
1
Click the intelligent thermal sensor assembly on the indoor unit.