2
|
Components
Service manual
57
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
1
If needed, remove any parts or insulation to create more space for the
removal.
2
Pull up the expansion valve motor to remove it from the expansion valve
body.
INFORMATION
It may be needed to turn the expansion valve coil 1/8 turn counter clockwise to
unlock it. Make sure to note the correct orientation (position) of the expansion valve
coil before removal.
a
b
a
Expansion valve motor
b
Expansion valve motor harness
INFORMATION
The expansion valve and motor can have a different configuration / layout.
3
Cut all tie straps that fix the expansion valve motor harness.
4
Disconnect the expansion valve motor connector from the main PCB.
5
To install the expansion valve motor, see
56].
To remove the expansion valve body
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
Prerequisite:
If needed, remove any parts or insulation to create more space for
the removal.
1
Remove the expansion valve motor, see
56].
2
Remove the putty. Keep for re-use.