G
as
f
urnaCe
www.DaikinApplied.com 61
IM 777-18 • SKYLINE OUTDOOR AIR HANDLER
BACnet Points
Table 29: Analog Variables
BMS Address
Description
Read/Write
Variable name
2
Burner Cmd Signal to burner
R
Burner_cmd
3
command to VAV dampers
R
BurnerDamperCmd
4
Customer Burner Cmd input Signal
R
Burner_cmd_in
13
pco board temp
R
pcoTemp
Table 30: Integer Variables
BMS Address
Description
Direction
Variable name
9
Profile pressure /1000
R
profilePressure
95
Current minute
R
CURRENT_MINUTE
96
Current hour
R
CURRENT_HOUR
97
Current year
R
CURRENT_YEAR
98
Current month
R
CURRENT_MONTH
99
Current day
R
CURRENT_DAY
Table 31: Digital Variables
BMS Address
Description
Direction
Variable name
1
customer’s burner enable input
R
Cust_Brnr_Enable_In
2
Main Flame
R
MainFlame
3
burner enabled
R
burner_ena
13
External Fault
R
mExternal_Flt
25
General Alarm
R
gen_alarm
27
used to reset alarms in logic
R/W