IM 777-18 • SKYLINE OUTDOOR AIR HANDLER 50 www.DaikinApplied.com
G
as
f
urnaCe
Recovery from Lockout
1. If the thermostat (controller) is still calling for heat one
hour after a lockout occurs, the control will automatically
reset and initiate a call for heat sequence.
2. The ignition control may also be manually reset,
removing power (24V) to IC terminal 24VAC for 5
seconds then restoring power.
LED Indications, Normal Operation
• Green, ½ sec ON, ½ sec OFF: Pre-purge, Inter-purge,
Post-purge
• Green, blinking rapidly: Trial for ignition
• Green, on solid: Flame detected, pilot/main burners on
ERROR CODES - Red Flashes Error Definition Error Type
•
1 flash, then pause - No flame in trial time Lockout
•
2 flashes, then pause - Flame sense stuck on Lockout
•
3 flashes, then pause - Pilot/Main relay failure Lockout
•
4 flashes, then pause - Repetitive flame loss error
Lockout
•
5 flashes, then pause - Rollout error Lockout
•
6 flashes, then pause - APS Airflow error Lockout
•
7 flashes, then pause - Internal control error Lockout
• On Solid Red - Line Voltage/Frequency Error Standby
Figure 81: HM/HD Series – SN Control (Staged Control)
BLU
WHT (Com)
YEL
5
L1
L2
GRY
BLU
24V
BLK
AIR SWITCH -HI
GRY
BLU
YEL
APS-2
GRY
BLK
WHT
BLU
BLU
4
115 VAC
Hot
Neut
40 VA
XFMR 1
Capable Controls – Series 5 Ignition Control
BLU
YEL
24VAC Alarm
Indicator
YEL
Gnd
(V2)
Gnd
Syst.
Alarm
YEL
COM
2 STG GAS VALVE
LO
HI
WHT
FLAME
SENSOR
ROR
IGNITER
SPARK
Series 5 Ignition Control
Spark
MV
24V
APS
(PSW)
T-Stat
Sense
3
PUR
HI LIMIT
PUR
APS-1
AIR SWITCH -LO
ORG
ORG
ORG
ORG
ROLL OUT
SWITCH
ROLL OUT
SWITCH (2)
Maxitrol
SC40
T1
T2
T3
T4
T5
T6
T7
T8
COM
T9
HAPS
EST
R1
24V
E Valve
(+)
(-)
T10
T11
(-)
(+)
T1
T2
T' STAT
Factory
Jumper
Customer
Interlocks
(See Note)
EX
A
Va
lv
e
(+)
(-)
(+)
(-)
24V SIG
YEL
BLU
BLU
YEL
0 – 10 VDC Analag Iput
(Polarity Sensitive)
YEL
YEL
BLU
RED
BLK
GRY
BLU
YEL
IGNITION CONTROL
L1
IND
BLK
BLK
HI
DRAFT INDUCER
RED
LO
BLK
WHT
4
2
Br/W
CR1
1
3
YEL
Br/W
J1
Shunted
See Notes for Dip
Switch Setting
(2)
2
nd
ROLLOUT SWITCH ON HORIZONTAL BURNER TRAY ONLY
CUSTOMER PROVIDED COMPONENT
CUSTOMER / FIELD WIRING
INTERNAL TERMINAL CONNECTION
1
EXTERNAL TERMINAL CONNECTION
3
LEGEND:
BLU
BLU
CR1
1 2 3 4
ON
Notes:
1.) If Customer safety interlocks provided,
wire in series from Terminal 3 to T1&
remove factory jumper
2.) Dip Switch setting for 0-10VDC Analog
BLU
BLK
YEL
PUR
BLU
1
2
24V
(2)
2
nd
ROLLOUT SWITCH ON HORIZONTAL BURNER TRAY ONLY
BLU
WHT
CUSTOMER PROVIDED COMPONENT
CUSTOMER / FIELD WIRING
YEL
R
C
5
BLU
BLU
INTERNAL TERMINAL CONNECTION
1
EXTERNAL TERMINAL CONNECTION
3
GRY
1/2
TR1 TIMER RELAY TERMINAL CONNECTION
1/2
3/4
6
AIR SWITCH -HI
3
ORG
ORG
YEL
BLU
TIMER RELAY
–
TR1-090LH15
Factory
Jumper
4
115 VAC
BLK
WHT
BLU
External Safety
Interlocks
YEL
GRY
PUR
40VA
ORG
ORG
ROLL OUT
SWITCH
ROLL OUT
SWITCH (2)
HI LIMIT
PUR
WHT
FLAME
SENSOR
ROR
IGNITER
SPARK
Series 5 Ignition Control
Spark
MV
24V
APS
(PSW)
T-Stat
Sense
APS-1
T2
T' STAT
T1
YEL
24VAC Alarm
Indicator
YEL
Gnd
(V2)
Gnd
Syst.
Alarm
YEL
COM
2 STG GAS VALVE
LO
HI
Capable Controls – Series 5 Ignition Control
IGNITION CONTROL
Not Used
BLK
DRAFT INDUCER
L1
IND
RED
BLK
WHT