Method of Field Set (Reset after Maintenance Inspection/Repair)
SiE25-110
46
Field Setting
1.5
Detailed Explanation of Setting Modes
1.5.1 Air Flow Adjustment - Ceiling height
Make the following setting according to the ceiling height. The setting position No. is set to “01”
at the factory.
In the Case of FAYP
In the Case of FHYCP (50 ~ 71 class), FUYP
In the Case of FHYCP (100 ~ 140 class)
1.5.2 Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”
Setting Table
1.5.3 Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
∗
1
FHYCP only 5,000 hrs.,
∗
2 FHYCP only 2,500 hrs.
Mode No.
Setting Switch
No.
Setting Position
No.
Setting
13(23)
0
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
No. of Air Outlets Used
4-way Outlets
3-way Outlets
2-way Outlets
Ceiling
Height
01 Standard (N)
Lower than 2.7 m
Lower than 3.0 m
Lower than 3.5 m
02 High Ceiling
(H)
Lower than 3.0 m
Lower than 3.3 m
Lower than 3.8 m
03 Higher Ceiling
(S)
Lower than 3.5 m
Lower than 3.5 m
—
No. of Air Outlets Used
4-way Outlets
3-way Outlets
2-way Outlets
Ceiling
Height
01 Standard (N)
Lower than 3.2 m
Lower than 3.6 m
Lower than 4.2 m
02 High Ceiling
(H)
Lower than 3.6 m
Lower than 4.0 m
Lower than 4.2 m
03 Higher Ceiling
(S)
Lower than 4.2 m
Lower than 4.2 m
—
Mode No.
First Code No.
Second Code
No.
Setting
13 (23)
1
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Filter Specs.
Setting
Standard
Long Life
Ultra Long Life Filter
Contamination Light
01
200 hrs.
2,500 hrs.
∗
1
10,000 hrs.
Contamination Heavy
02
100 hrs.
1,100 hrs.
∗
2
5,000 hrs.
Содержание SkyAir Super Inverter 70
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...