Function Details
SiE25-110
76
Function and Operation
Condensation
Avoidance
Control (FHYP
Model Only)
Note
1. Regardless of thermostat ON or OFF, the control can be functioned with the operation mode
of “ cooling ( automatic cooling ) ” or “ programmed drying ”.
2. The function is not provided for models other than FHYP71~125B.
Outdoor Unit
Identification
Function
If the indoor unit is for both a heat pump and cooling only type, this function differentiates
whether the outdoor unit is functioning as a heat pump or cooling only unit, and automatically
decides the which operation modes can be set.
Operation modes which can be set
Heat pump : Fan / cool / dry / auto / heat
Drain Pump
Control (FHYCP
and FHYP
(OPTION) Only)
1. During cooling and program dry operation modes, the control function turns on the drain
pump according to the compressor operation. When the compressor turns OFF, the drain
pump continues operating for additional 5 minutes.
2. During cooling and microcomputer-controlled operation modes as well as in the initial stage
of heating operation, the control function detects the water level in the drain pan, and
performs an error shutdown process if the water level is abnormal.
(A) Drain pan water level detection system (water level sensor type) : cassette type
i) During operation startup
After continuous 30 minutes of operation with downward
horizontal blade position, change the blade position to
level, and after one hour, the unit operation can be reset.
The unit operation can be reset with changing operation
mode into "heating" or "fan", changing air flow direction or
turning "ON" or "OFF" the unit operation.
(S1117)
Continuous 30 minutes operation of cooling
One hour drying
ON operation
Water level abnormality
Normal
Drain pan
ON
OFF
Compressor
ON
OFF
Drain pump
Abnormal
Normal
Error processing
Note 2)
1 min
3 min
2 min
5 sec
5 min
Содержание SkyAir Super Inverter 70
Страница 11: ...SiE25 110 2...
Страница 15: ...Model Name and Power Supply SiE25 110 6 Model Name and Power Supply...
Страница 16: ...SiE25 110 Functions 7 Part 2 Functions 1 List of Functions 8 1 1 Functions 8...
Страница 31: ...Specifications SiE25 110 22 Specifications...
Страница 35: ...Wired Remote Controller SiE25 110 26 Remote Controller 1 2 Installation...
Страница 36: ...SiE25 110 Wired Remote Controller Remote Controller 27...
Страница 39: ...Wireless Remote Controller SiE25 110 30 Remote Controller...
Страница 63: ...Settings Concerning Maintenance SiE25 110 54 Field Setting FUYP...
Страница 64: ...SiE25 110 Settings Concerning Maintenance Field Setting 55 FHYP...
Страница 65: ...Settings Concerning Maintenance SiE25 110 56 Field Setting FAYP...
Страница 67: ...Settings Concerning Maintenance SiE25 110 58 Field Setting RZP100 125DV1 E RZP100DVAL E...
Страница 68: ...SiE25 110 Settings Concerning Maintenance Field Setting 59 RZP125 140DTAL...
Страница 107: ...Operation Range SiE25 110 98 Function and Operation 5 Operation Range 5 1 Operation Limits...
Страница 133: ...Procedure of Self Diagnosis by Remote Controller SiE25 110 124 Troubleshooting...
Страница 238: ...SiE25 110 Piping Diagrams Appendix 229 1 2 Twin System RZP100D RZP125D 3D034162...
Страница 240: ...SiE25 110 Wiring Diagrams Appendix 231 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 3D027503...
Страница 241: ...Wiring Diagrams SiE25 110 232 Appendix FUYP71BV1 FUYP100BV1 FUYP125BV1 3D027747...
Страница 242: ...SiE25 110 Wiring Diagrams Appendix 233 FAYP71BV1 FAYP100BV1 3D027748...
Страница 243: ...Wiring Diagrams SiE25 110 234 Appendix 2 2 Outdoor Units 2 2 1 50Hz RZP71DV1 3D032604...
Страница 244: ...SiE25 110 Wiring Diagrams Appendix 235 RZP100DV1 RZP125DV1 3D032603...
Страница 245: ...Wiring Diagrams SiE25 110 236 Appendix 2 2 2 60Hz RZP71DVAL 3D032880B...
Страница 246: ...SiE25 110 Wiring Diagrams Appendix 237 RZP100DVAL 3D032881B...
Страница 247: ...Wiring Diagrams SiE25 110 238 Appendix RZP125DTAL RZP140DTAL 3D032882B...
Страница 251: ...SiE25 110 iv Index...