2.24 Actuation of Low Pressure Sensor
Remote
Controller
Display
E4
Applicable
Models
RZR, RZQ
Method of Error
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Error Decision
Conditions
Error is generated when the low pressure is dropped during compressor operating.
Operating pressure: 10 psi
Supposed
Causes
Abnormal drop of low pressure (Lower than 10 psi)
Defective low pressure sensor
Defective outdoor unit PCB
Stop valve is not opened.
Clogged filter