background image

24

English

BEFORE YOU CALL YOUR SERVICER

Check the thermostat to confirm that it is properly set.

Wait  15  minutes.  Some  devices  in  the  outdoor  unit  or  in
programmable thermostats will prevent compressor opera-
tion  for  awhile,  and  then  reset  automatically.  Also,  some
power companies will install devices which shut off air con-
ditioners for several minutes on hot days. If you wait sev-
eral minutes, the unit may begin operation on its own.

Check the electrical panel  for tripped circuit breakers  or
failed fuses. Reset the circuit breakers or replace fuses as
necessary.

Check the disconnect switch near the indoor furnace or blower to confirm that it is closed.

Check for obstructions on the outdoor unit . Confirm that it has not been covered on the sides or the top. Remove any obstruc-
tion that can be safely  removed. If  the unit is covered with dirt or debris, call a qualified servicer to clean it.

Check for blockage of the indoor air inlets and outlets. Confirm that they are open and have not been blocked by objects (rugs,
curtains or furniture).

Check the filter. If it is dirty, clean or replace it.

Listen for any unusual noise(s), other than normal operating noise, that might be coming from the outdoor unit.   If you hear
unusual noise(s) coming from the unit, call a qualified servicer.

AIR HANDLER

AIR HANDLER HOMEOWNER’S

 

ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed before the heating and cooling seasons begin by a 

qualified servicer

.

REPLACE OR CLEAN FILTER

IMPORTANT NOTE: 

Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of

efficiency, equipment damage and possible fire.

An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort
system clean. A dirty coil could cause poor operation and/or severe equipment damage.

Your air filter or filters could be located in your furnace, in a blower unit, or in “filter grilles” in your ceiling or walls. The installer of
your air conditioner or heat pump can tell you where your filter(s) are, and how to clean or replace them.

Check your filter(s) at least once a month. When they are dirty, replace or clean as required. Disposable type filters should be
replaced. Reusable type filters may be cleaned.

You  may  want  to  ask  your  dealer  about  high  efficiency  filters.  High  efficiency  filters  are  available  in  both  electronic  and  non-
electronic types. These filters can do a better job of catching
small airborne particles.

MOTOR

S

Indoor and outdoor fan motors are permanently lubricated and
do not require additional oiling.

ALUMINUM INDOOR COIL CLEANING

(QUALIFIED SERVICER ONLY)

This  unit  is  equipped  with  an  aluminum  tube  evaporator  coil.
The safest way to clean the evaporator coil is to simply flush the coil with water. This cleaning practice remains as the recom-
mended cleaning method for both copper tube and aluminum tube residential evaporator coils.

It has been determined that many coil cleaners and drain pan tablets contain corrosive chemicals that can be harmful to aluminum
tube and fin evaporator coils. Even a one-time application of these corrosive chemicals can cause premature aluminum evaporator
coil failure. Any cleaners that contain corrosive chemicals including, but not limited to, chlorine and hydroxides, should not be used.

An alternate cleaning method is to use one of the products listed in TP-109* to clean the coils. The cleaners listed are the only
agents deemed safe and approved for use to clean round tube aluminum coils. TP-109 is also available on the web site in Partner
Link > Service Toolkit.

NOTE: Ensure coils are rinsed well after use of any chemical cleaners.

Содержание SkyAir FTQ18TAVJUA

Страница 1: ...English Fran ais Espa ol ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTU...

Страница 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Страница 3: ...mmediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage may occur Do not touch the refrigerant pipes during and immediately after op...

Страница 4: ...serviceman Improper installation could lead to leaks and in worse cases electric shock or fire Use of unspecified parts could lead to the unit failing leaks and in worse cases electric shock or fire B...

Страница 5: ...tion site where the following conditions are fulfilled and meets with your customer s approval Where optimum air distribution can be ensured Where nothing blocks air passage Where condensate can be pr...

Страница 6: ...L LEFT INSTALLATION No field modifications are permissible for this application Refer to Figure 7 and 8 for the location of the components referenced in the following steps Drain port labeled B in Fig...

Страница 7: ...ew Side view Screw Front view Side view mount mount NOTE DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS 3 Slide the coil as...

Страница 8: ...ure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Blower Access Panel Coil Access Panel Tubing Panel UV Knockout Filter Access Panel NOTE If removing only the coil acce...

Страница 9: ...nt piping according to the installation environment If the temperature or humidity in the product installation location might reach 86 F or 80 respectively Condensation may form on the surface of the...

Страница 10: ...g connections referring to Fig 13 Do not leave a gap Gas piping Piping heat insulation material Liquid piping Air handler Figure 13 Be sure to insulate any field piping all the way to the piping conne...

Страница 11: ...roper drainage Some installation may require a field fabricated or field supplied secondary drain pan under the coil cabinet enclosure The installation must include a P style trap that is located as c...

Страница 12: ...rmed by an authorized electrician Install a wiring interrupter or ground fault circuit interrupter for the power wiring To avoid short circuiting the power supply wire be sure to use insulated termina...

Страница 13: ...r wire connection from the 240V terminal to the 208V terminal on both transformers 8 4 ELECTRICAL CHARACTERISTICS Hz Volts MCA MOP HP FLA Cooling Heating 60 208 230V 4 9 15 1 2 3 9 215 215 60 208 230V...

Страница 14: ...fore installing the Heat Kit uninstall the transformer sub assembly Figure 19 Make sure to unplug 12 pin connector before uninstalling the transformer sub assembly Follow the Heat Kit Installation Man...

Страница 15: ...RECAUTIONS Daisy chain wiring is needed when using group control and 2 remote controllers at the same time Connect the indoor unit at the end of the crossover wire P1 P2 to remote controller 2 SUB Fig...

Страница 16: ...settings may have to be performed using the remote controller depending on the type of installation 1 Make sure the electric component box covers are closed on the indoor and outdoor units 2 Dependin...

Страница 17: ...gging and also the time that is set 01 02 0 low high 10000 5000 ON OFF Mode No 10 20 FIRST CODE NO SECOND CODE NO Filter dirt 1 low high 3 Displayed time units hours Filter sign display 2500 1250 9 4...

Страница 18: ...CFM can be estimated from the TR formula above See Specification Sheet and or Service Manual for more information 11 21 3 XX XX 01 02 07 08 Heater Operation Electric Heater with Heat Pump not allowed...

Страница 19: ...XX Choose dry mode settings as per following table XX 01 02 DRY mode Set Point Room Temperature Set Point became same as cooling mode set point Mode No 14 24 First Code No 5 Second Code No XX 10 ACCES...

Страница 20: ...gs 11 TEST RUN Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the...

Страница 21: ...R GREEN WH WHITE PU PURPLE LOW VOLTAGE LOW VOLTAGE FIELD HIGH VOLTAGE HIGH VOLTAGE FIELD JUNCTION TERMINAL PLUG CONNECTION EQUIPMENT GND FIELD GROUND 0140A00500 A X1A X3A X38A BS1 X12A X13A HAP X8A TH...

Страница 22: ...22 English THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 23: ...23 English THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 24: ...perly maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in you...

Отзывы: