background image

17

English

9.2

REMOTE CONTROL SETTING (T1, T2)

Forced off and ON/OFF operation should be selected by selecting
the SECOND CODE NO. as shown in Table 5.

External ON/OFF

input

Mode

No.

FIRST

CODE NO.

SECOND

CODE NO.

Forced Off

 

01*

ON/OFF Operation

02

System/Equipment Protection

03

12/(22)

1

* Factory Set

Table 5

Input A of forced off and ON/OFF operation work as shown in
Table 6.

Forced Off

ON/OFF Operation

System/

Equipment

Protection

Input A "on" to force a stop
(remote controller
reception prohibited)

Unit operated by changing
input A from "off" to "on"

Input A "off" to allow
remote controller

Unit stopped by changing
input A from "on" to "off"

Input A

 "off"

to stop 
system

Table 6

9.3

SETTING THE FILTER SIGN DISPLAY

INTERVAL

Explain the following to the customer if the filter dirt settings
have been changed.

The filter sign display time is set to 2500 hours (equivalent
to 1 year’s use) when shipped.

The settings can be changed to not display.

When installing the unit in a dusty place, set the filter sign
display time to shorter intervals (1,250 hours).

Explain to the customer that the filter needs to be cleaned
regularly to prevent clogging and also the time that is set.

01

02

0

low

high

10000/

5000

ON

OFF

Mode

No.

10 (20)

FIRST CODE NO.

SECOND CODE

NO.

Filter dirt

1 (low/high)

3

Displayed time

(units: hours)

Filter sign

display

2500/

1250

9.4

RETURN AIR FILTER

Each installation must include a return air filter. This filtering may
be performed at the air handler using the factory filter rails or
externally such as a return air filter grille. When using the factory
filter  rails,  a  nominal  16x20x1",  20x20x1"  or  24x20x1"  (actual
dimension must be less than 23-½”x20") filter can be installed.
Washable  versions  are  available  through  your  local  Daikin
distributor.

Do not operate this product without all the ductwork attached.

9.5

ELECTRIC HEAT

Refer to the installation manual provided with the electric heat
kit for the correct installation procedure. All electric heat must be
field  installed.  If  installing  this  option,  the  ONLY  heat  kits  that
are permitted to be used are the Daikin produced HKS series.
Refer to the air handler unit’s Serial and Rating plate or the HKS
specification sheets to determine the heat kits compatible with a
given air handler. No other accessory heat kit besides the HKS
series may be installed in these air handlers. The heating mode
temperature rise is dependent upon the system airflow, the supply
voltage, and the heat kit size (kW) selected.

Содержание SkyAir FTQ18TAVJUA

Страница 1: ...English Fran ais Espa ol ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT THE MANUFACTU...

Страница 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Страница 3: ...mmediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage may occur Do not touch the refrigerant pipes during and immediately after op...

Страница 4: ...serviceman Improper installation could lead to leaks and in worse cases electric shock or fire Use of unspecified parts could lead to the unit failing leaks and in worse cases electric shock or fire B...

Страница 5: ...tion site where the following conditions are fulfilled and meets with your customer s approval Where optimum air distribution can be ensured Where nothing blocks air passage Where condensate can be pr...

Страница 6: ...L LEFT INSTALLATION No field modifications are permissible for this application Refer to Figure 7 and 8 for the location of the components referenced in the following steps Drain port labeled B in Fig...

Страница 7: ...ew Side view Screw Front view Side view mount mount NOTE DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS 3 Slide the coil as...

Страница 8: ...ure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Blower Access Panel Coil Access Panel Tubing Panel UV Knockout Filter Access Panel NOTE If removing only the coil acce...

Страница 9: ...nt piping according to the installation environment If the temperature or humidity in the product installation location might reach 86 F or 80 respectively Condensation may form on the surface of the...

Страница 10: ...g connections referring to Fig 13 Do not leave a gap Gas piping Piping heat insulation material Liquid piping Air handler Figure 13 Be sure to insulate any field piping all the way to the piping conne...

Страница 11: ...roper drainage Some installation may require a field fabricated or field supplied secondary drain pan under the coil cabinet enclosure The installation must include a P style trap that is located as c...

Страница 12: ...rmed by an authorized electrician Install a wiring interrupter or ground fault circuit interrupter for the power wiring To avoid short circuiting the power supply wire be sure to use insulated termina...

Страница 13: ...r wire connection from the 240V terminal to the 208V terminal on both transformers 8 4 ELECTRICAL CHARACTERISTICS Hz Volts MCA MOP HP FLA Cooling Heating 60 208 230V 4 9 15 1 2 3 9 215 215 60 208 230V...

Страница 14: ...fore installing the Heat Kit uninstall the transformer sub assembly Figure 19 Make sure to unplug 12 pin connector before uninstalling the transformer sub assembly Follow the Heat Kit Installation Man...

Страница 15: ...RECAUTIONS Daisy chain wiring is needed when using group control and 2 remote controllers at the same time Connect the indoor unit at the end of the crossover wire P1 P2 to remote controller 2 SUB Fig...

Страница 16: ...settings may have to be performed using the remote controller depending on the type of installation 1 Make sure the electric component box covers are closed on the indoor and outdoor units 2 Dependin...

Страница 17: ...gging and also the time that is set 01 02 0 low high 10000 5000 ON OFF Mode No 10 20 FIRST CODE NO SECOND CODE NO Filter dirt 1 low high 3 Displayed time units hours Filter sign display 2500 1250 9 4...

Страница 18: ...CFM can be estimated from the TR formula above See Specification Sheet and or Service Manual for more information 11 21 3 XX XX 01 02 07 08 Heater Operation Electric Heater with Heat Pump not allowed...

Страница 19: ...XX Choose dry mode settings as per following table XX 01 02 DRY mode Set Point Room Temperature Set Point became same as cooling mode set point Mode No 14 24 First Code No 5 Second Code No XX 10 ACCES...

Страница 20: ...gs 11 TEST RUN Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the...

Страница 21: ...R GREEN WH WHITE PU PURPLE LOW VOLTAGE LOW VOLTAGE FIELD HIGH VOLTAGE HIGH VOLTAGE FIELD JUNCTION TERMINAL PLUG CONNECTION EQUIPMENT GND FIELD GROUND 0140A00500 A X1A X3A X38A BS1 X12A X13A HAP X8A TH...

Страница 22: ...22 English THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 23: ...23 English THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 24: ...perly maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in you...

Отзывы: