Overview of the heating mode functions
ESIE02–01
2–50
Part 2 – Functional Description
3
1
2
4
5
Normal control
The optimum discharge pipe temperature is calculated based on:
■
Indoor and outdoor heat exchanger temperature
■
Actual discharge pipe temperature
■
Outdoor ambient temperature.
The expansion valve is controlled in order for the discharge temperature to approach the optimum
temperature.
Used input
The motor operated valve control uses the following inputs:
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Outdoor thermistor
—
R1T
Outdoor heat exchanger thermistor
—
R2T
Discharge pipe thermistor
—
R3T
Indoor heat exchanger thermistor
R2T
—
Содержание Sky Air R-407C
Страница 1: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Страница 2: ......
Страница 3: ...ESIE02 01 Service Manual Sky Air R 407C B series SV p p p...
Страница 4: ......
Страница 16: ...Introduction ESIE02 01 xii 3 1 4 5...
Страница 18: ...ESIE02 01 1 2 Part 1 System Outline 3 1 1 5...
Страница 42: ...General Outline Outdoor Units ESIE02 01 1 26 Part 1 System Outline 3 1 1 4 5...
Страница 49: ...ESIE02 01 General Outline Indoor Units Part 1 System Outline 1 33 3 1 4 5...
Страница 72: ...General Outline Indoor Units ESIE02 01 1 56 Part 1 System Outline 3 1 1 4 5...
Страница 86: ...Specifications ESIE02 01 1 70 Part 1 System Outline 3 1 1 4 5...
Страница 110: ...ESIE02 01 1 94 Part 1 System Outline...
Страница 130: ...Switch Box Layout ESIE02 01 1 114 Part 1 System Outline 3 1 1 4 5...
Страница 180: ...PCB Layout ESIE02 01 1 164 Part 1 System Outline 3 1 1 4 5...
Страница 182: ...ESIE02 01 2 2 Part 2 Functional Description 3 1 2 5...
Страница 204: ...General Functionality ESIE02 01 2 24 Part 2 Functional Description 3 1 2 4 5...
Страница 216: ...Overview of the cooling mode functions ESIE02 01 2 36 Part 2 Functional Description 3 1 2 4 5...
Страница 232: ...ESIE02 01 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 294: ...Error Codes System Malfunctions ESIE02 01 3 64 Part 3 Troubleshooting 3 1 3 4 5...