ELECTRICAL WIRING CONNECTION

IMPORTANT :

 

*  The figures shown in the table are for information purpose only. They should be checked and selected 

to comply with the local/national codes of regulations. This is also subject to the type of installation and 
conductors used.

 

**  The appropriate voltage range should be checked with label data on the unit.

N

OF

4WV

N1

L

COMP

N

OF

4WV

COMP

Heat Pump Unit (Single Phase)

Model

Indoor (ATYN)

20J 25J 35J 50J 60J

Outdoor (ARYN)

20C 25C 35C 50C 60C

Voltage range**

220-240V/~/50Hz + 

!

 

Power supply cable size* mm

2

Number of conductors

1.5

3

2.5

3

Interconnection cable size* mm

2

Number of conductors

1.5

5

2.5

5

Recommended fuse/circuit breaker rating 

A

15

20

Outdoor Unit 

Terminal Block

Indoor Unit 

Terminal Block

Interconnection cable

There must be an all pole disconnection 
in the supply mains with a contact 

separation of at least 3mm.

!

Outdoor coil sensor connection wire 
(8m long) attached in the indoor unit

N / L2
L / L1

Power 
Supply

Main 

Switch

Fuse / Circuit 

Breaker

Power Supply Cable

Attach insulation sleeve

Round crimp-style terminal

Electric wire

All wires must be 

fi

 rmly connected.

All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement.
Make sure no external pressure is applied to the terminal connectors and wires.
Make sure all the covers are properly 

fi

 xed to avoid any gap.

Use round crimp-style terminal for connecting wires to the power supply terminal block. Connect the wires by matching 
to the indication on terminal block. (Refer to the wiring diagram attached on the unit).







Connect wires of the 
same gauge to both side.

Do not connect wires of the 
same gauge to one side.

Do not connect wires 
of different gauges.

Used the correct screwdriver for terminal screws tightening. Unsuitable screwdrivers can damage the screw head.
Over tightening can damage the terminal screws.
Do not connect wire of different gauge to same terminal.
Keep wiring in an orderly manner. Prevent the wiring from obstructing other parts and the terminal box cover.




1 IM-5WMJR-0515(0)-DAIKIN SIESTA11   11

1 IM-5WMJR-0515(0)-DAIKIN SIESTA11   11

6/1/15   3:20:43 PM

6/1/15   3:20:43 PM

Содержание Siesta ATYN20LV1

Страница 1: ...1 ATYN25LV1 ARYN25LV1 ATYN35LV1 ARYN35LV1 ATYN50LV1 ARYN50LV1 ATYN60LV1 ARYN60LV1 WALL MOUNTED R410A SPLIT TYPE AIR CONDITIONER IM 5WMJR 0515 0 DAIKIN SIESTA Part No R08019043338 Installation Manual R...

Страница 2: ......

Страница 3: ...WS INSIDE LOUVER SIGNAL RECEIVER INDOOR UNIT ON OFF SWITCH ROOM TEMPERATURE THERMISTOR INSIDE NAME PLATE TERMINAL BLOCK WITH EARTH TERMINAL F E J G G L D B K M A Gas pipe end INSTALLATION PLATE 20 25...

Страница 4: ...1065 310 224 190 173 61 40 45 48 91 219 580 45 Recommended mounting plate retention spots 7 spots in all Dimension Model A B C D E F G H I J K L M 20 25 35J 800 288 206 104 141 30 46 55 56 153 181 20...

Страница 5: ...C G H I J Dimension Model O P Q R S T 20C 22 3 19 65 80 30 25 35C 18 3 19 65 80 30 T All dimensions are in mm B A Q P R S D O K L L M N F E C G H I J N Dimension Model A B C D E F G H I J K L 50C 855...

Страница 6: ...om TVs and radios to prevent distorted pictures and static Depending on the type and source of the electrical waves static may be heard even when more than 1m away Please take note of the following im...

Страница 7: ...crews 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down INSTALLATION DIAGRAM Indoor unit Service lid Cut thermal insulation pipe to an appropriate length and wrap it...

Страница 8: ...age Please remove side plate when connecting the piping and connecting cord PUSH PULL UP BASE A DRAIN ELBOW DRAIN ELBOW PLUG INSTALLATION OF THE OUTDOOR UNIT The outdoor unit must be installed in such...

Страница 9: ...ace for performance Required space Right back piping All dimensions are in mm Right bottom piping Right side piping Remove pipe port cover here for right side piping Left back piping Left side piping...

Страница 10: ...or Unit Push up the marked area at the lower part of the front grille to release the claws Mounting plate Interconnecting wires Hang indoor unit s hook here Wire guide When stripping the ends of inter...

Страница 11: ...m 12 12 12 20 20 Max Allowable Elevation E m 5 5 5 15 15 Gas Pipe Size mm in 9 52 3 8 9 52 3 8 12 70 1 2 12 70 1 2 15 88 5 8 Liquid Pipe Size mm in 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 Heat P...

Страница 12: ...firmly on the swaging block Match the centers of both the swaging block and the flaring punch then tighten the flaring punch fully Piping Connection To The Units Align the center of the piping and tig...

Страница 13: ...Supply Cable Attach insulation sleeve Round crimp style terminal Electric wire All wires must be firmly connected All wires must not touch the refrigerant piping compressor or any moving parts of the...

Страница 14: ...pressor Remove the caps from the valve and the service port Connect the center of the charging gauge to the vacuum pump Connect the charging gauge to the service port of the 3 way valve Start the vacu...

Страница 15: ...h an auto mode sensor whereby it will provide reasonable room temperature by switching automatically to either cool or heat mode according to the temperature set by the user ON OFF Cool Heat Timer Sle...

Страница 16: ...1 time Room air sensor contact Loose Short Call your dealer Blink E1 3 times Outdoor coil sensor open Call your dealer Blink E3 2 times Indoor coil sensor open Call your dealer Blink E2 1 time Compre...

Страница 17: ...ulting in drippings Overheating Protection for heat pump unit only In case the internal and or the external temperature is too high or that the filter is dirty and clogged up the refrigerant may be ov...

Страница 18: ...ing shaft is detached Slide the right rotating shaft to the left and pull it to the front side to remove it 2 Attach the front panel Align the right and left rotating shafts of the front panel with th...

Страница 19: ...erature is not high enough Discharge air flow has bad odour 4 Odours may be caused by cigarettes smoke particles perfume etc which might have adhered onto the coil Condensation on the front air grille...

Страница 20: ...MEMO...

Страница 21: ...2 1 XEMA A MEP 20 25 35J 1 2 A B C D E F G H I J K L M 20 25 35J 800 288 206 166 184 42 46 55 56 154 182 263 52 K ATYN A B C H I B F E J G G L D B K M A 20 25 35J 65 F 5...

Страница 22: ...L M 20 25 35J 800 288 206 104 141 30 46 55 56 153 181 207 52 A B C D E F G H I J K L M 50 60J 1065 310 224 190 173 61 40 45 48 91 219 580 45 D B G H J L M A K F I G F E 50 60J 7 5 65 E F G I K M L J...

Страница 23: ...521 250 485 175 36 95 93 86 68 441 130 111 15 O P Q R S T 20C 22 3 19 65 80 30 25 35C 18 3 19 65 80 30 T B A Q P R S D O K L L M N F E C G H I J N A B C D E F G H I J K L 50C 855 628 328 520 179 46 9...

Страница 24: ...2 4 H MAH E CTOPO HO 1 1 OFF...

Страница 25: ...2 5 M4 x 12L e 75 50 1 2 3 500...

Страница 26: ...2 6 2 A A H A B C D acc o e 300 1000 300 500 A B H 2 H pe c C D pe c...

Страница 27: ...2 7 50 50 75 c y ox K K 50 60J 20 25 35J K 20 25 35J 20 25 35J 50 60J 65...

Страница 28: ...173 61 310 61 48 45 580 1065 219 40 40 91 45 65 166 184 181 7 55 5 54 5 153 8 263 51 9 800 45 9 42 2 288 42 2 45 9 poc ep e ec ep o 50 60J 20 25 35J 5 65 7 65 5 104 141 30 46 56 181 800 55 207 52 153...

Страница 29: ...2 9 7 5 ATYN 20J 25J 35J 50J 60J ARYN 20C 25C 35C 50C 60C M L 3 Ma L 12 12 12 20 20 E 5 5 5 15 15 9 52 3 8 9 52 3 8 12 70 1 2 12 70 1 2 15 88 5 8 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 L E...

Страница 30: ...2 3 8 42 31 0 12 70 1 2 55 40 6 15 88 5 8 65 48 0 19 05 3 4 78 57 6 C D A 1 4 6 35 1 3 0 7 3 8 9 52 1 6 1 0 1 2 12 70 1 9 1 3 5 8 15 88 2 2 1 7 3 4 19 05 2 5 2 0 II III IV L 3 8 OD9 52 0 18 1 3 1 2 OD...

Страница 31: ...2 11 N OF 4WV N1 L COMP N OF 4WV COMP ATYN 20J 25J 35J 50J 60J ARYN 20C 25C 35C 50C 60C 220 240V 50 2 1 5 3 2 5 3 2 1 5 5 2 5 5 A 15 20 8 N L2 L L1 3 H07RN F...

Страница 32: ...2 12 R410A R410A 1 6 R22 R410A POE PVE R410A R22 R410A POE PVE R22 R410A R410A R410A R22 C 3 30 760 760 3 2 4 o 3 760 760 3 3...

Страница 33: ...2 13 ATYN 20 25 35 50 60J ON OFF 7 5 7 5 1 2 1 ATYN35J ARYN35C 12 4 5 4 5 x 9 40 5 1 R410A ATYN 20J 25J 35J 50J 60J ARYN 20C 25C 35C 50C 60C 20 16 16 19 16...

Страница 34: ...2 14 1 E1 3 E3 2 E2 1 E4 3 E5 6 E8 4 E9...

Страница 35: ...2 15 2 C 3 6 F 2 C 3 6 F 2 C 3 6 F 62 C 143 6 F 1 C 33 8 F HIGH HOT KEEP OFF INTERVAL ON X DB WB WB C DB C 46 43 19 14 19 23 DB C 15 20 27 WB C 18 10 9...

Страница 36: ...2 16 FRONT 2 1 3 4 2 2 1 2 c 3 CTOPO HO 40 104 F 1 2 3 1 2 40 104 F 1 2 1 2...

Страница 37: ...2 17 CTOPO HO 40 C 3 1 3 4 2 3 4 5 6 2 30 C 86 F...

Страница 38: ......

Страница 39: ......

Страница 40: ...contain herein at any time without prior notification P O Box 18674 Galleries 4 11th Floor Downtown Jebel Ali Dubai UAE Zandvoordestraat 300 B 8400 Oostende Belgium Importer for Turkey Allianz Plaza K...

Отзывы: