background image

6 Installation

Installer reference guide

15

RZQG71~Y1 + RZQSG100~Y1
Split system air conditioners
4P385522-1A – 2016.10

6.4.3

Guidelines when connecting the
refrigerant piping

Take the following guidelines into account when connecting pipes:

▪ Coat  the  flare  inner  surface  with  ether  oil  or  ester  oil  when

connecting  a  flare  nut.  Tighten  3  or  4  turns  by  hand,  before
tightening firmly.

▪ Always use two wrenches together when loosening a flare nut.

▪ Always  use  a  spanner  and  torque  wrench  together  to  tighten  the

flare nut when connecting the piping. This to prevent nut cracking
and leaks.

a

b

c

d

a

Torque wrench

b

Spanner

c

Piping union

d

Flare nut

Piping size

(mm)

Tightening

torque (N•m)

Flare

dimensions (A)

(mm)

Flare shape

(mm)

Ø6.4

15~17

8.7~9.1

R=0.4~0.8

45° ±2

90°±2

A

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

Ø15.9

63~75

19.3~19.7

Ø19.1

90~110

23.6~24.0

6.4.4

Pipe bending guidelines

Use  a  pipe  bender  for  bending.  All  pipe  bends  should  be  as  gentle
as possible (bending radius should be 30~40 mm or larger).

6.4.5

To flare the pipe end

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

1

Cut the pipe end with a pipe cutter.

2

Remove burrs with the cut surface facing downward so that the
chips do not enter the pipe.

a

b

a

Cut exactly at right angles.

b

Remove burrs.

3

Remove  the  flare  nut  from  the  stop  valve  and  put  the  flare  nut
on the pipe.

4

Flare  the  pipe.  Set  exactly  at  the  position  as  shown  in  the
following illustration.

A

Flare tool for

R410A (clutch

type)

Conventional flare tool

Clutch type

(Ridgid-type)

Wing nut type

(Imperial-type)

A

0~0.5 mm

1.0~1.5 mm

1.5~2.0 mm

5

Check that the flaring is properly made.

a

b

c

a

Flare’s inner surface must be flawless.

b

The pipe end must be evenly flared in a perfect circle.

c

Make sure the flare nut is fitted.

6.4.6

To braze the pipe end

The  indoor  unit  and  outdoor  unit  have  flare  connections.  Connect
both  ends  without  brazing.  If  brazing  should  be  needed,  take  the
following into account:

▪ When  brazing,  blow  through  with  nitrogen  to  prevent  creation  of

large  quantities  of  oxidised  film  on  the  inside  of  the  piping.  This
film adversely affects valves and compressors in the refrigerating
system and prevents proper operation.

▪ Set the nitrogen pressure to 20 kPa (0.2 bar)(just enough so it can

be felt on the skin) with a pressure-reducing valve.

a

b

c

d

e

f

f

a

Refrigerant piping

b

Part to be brazed

c

Taping

d

Manual valve

e

Pressure-reducing valve

f

Nitrogen

▪ Do NOT use anti-oxidants when brazing pipe joints.

Residue can clog pipes and break equipment.

▪ Do  NOT  use  flux  when  brazing  copper-to-copper  refrigerant

piping.  Use  phosphor  copper  brazing  filler  alloy  (BCuP),  which
does not require flux.
Flux  has  an  extremely  harmful  influence  on  refrigerant  piping
systems. For instance, if chlorine based flux is used, it will cause
pipe  corrosion  or,  in  particular,  if  the  flux  contains  fluorine,  it  will
deteriorate the refrigerant oil.

6.4.7

Using the stop valve and service port

To handle the stop valve

Take the following guidelines into account:

▪ The stop valves are factory closed.

▪ The following illustration shows each part required in handling the

valve.

c
d

a

b

a

Service port and service port cap

b

Valve stem

c

Field piping connection

d

Stem cap

▪ Keep both stop valves open during operation.

Содержание RZQG71L9V1B

Страница 1: ...rs English Installer reference guide Split system air conditioners RZQG71L9V1B RZQG100L9V1B RZQG125L9V1B RZQG140L9V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L9V1B RZQSG125L9V1B RZQ...

Страница 2: ...ng to the outdoor unit 16 6 4 9 To determine if oil traps are required 17 6 5 Checking the refrigerant piping 17 6 5 1 About checking the refrigerant piping 17 6 5 2 Precautions when checking the refr...

Страница 3: ...F BURNING Do NOT touch the refrigerant piping water piping or internal parts during and immediately after operation It could be too hot or too cold Give it time to return to normal temperature If you...

Страница 4: ...ion WARNING Make sure there is no oxygen in the system Refrigerant may only be charged after performing the leak test and the vacuum drying In case re charge is required refer to the nameplate of the...

Страница 5: ...esistant to high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do not connect wiring of different thicknesses to the...

Страница 6: ...allation What to do and know to install the system Commissioning What to do and know to commission the system after it is installed Hand over to the user What to give and explain to the user Maintenan...

Страница 7: ...L7 in combination with RZQG_V1 you also have to install the demand adaptor kit For installation instructions see the installation manual of the bottom plate heater Demand adaptor kit Can be used for t...

Страница 8: ...eaker 1 5 height of outdoor unit Mind the service space requirements when installing the windbreaker a b c d c d a Sea wind b Building c Outdoor unit d Windbreaker Strong winds 18 km h blowing against...

Страница 9: ...oil checking reference card This is available from your dealer 1 Put some residual oil from the piping on a piece of white paper 2 Compare the colours If the oil colour is Then Identical to or darker...

Страница 10: ...iquid piping 9 5 mm Gas piping 15 9 mm L1 pair twin triple double twin Model New a Existing b L1 liquid piping L1 gas piping RZQG71 Size down 6 4 mm 12 7 mm Standard 9 5 mm 15 9 mm Size up 12 7 mm RZQ...

Страница 11: ...m b 25 m 35 m b 3 Maximum allowable piping length Pair N A Twin L1 L2 L3 Limit 60 m 75 m 50 m Triple L1 L2 L3 L4 Limit 75 m 50 m Double twin L1 L2 L3 L4 L5 L6 L7 Limit 75 m 50 m 4 Maximum branch pipi...

Страница 12: ...because this unit is equipped with an inverter A phase advancing capacitor will reduce performance and may cause accidents WARNING All wiring must be performed by an authorized electrician and must co...

Страница 13: ...0 350 3 4 5 3 5 5 4 M12 a a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundatio...

Страница 14: ...ting the refrigerant piping to the indoor unit Installing oil traps Insulating the refrigerant piping Keeping in mind the guidelines for Pipe bending Flaring pipe ends Brazing Using the stop valves 6...

Страница 15: ...stration A Flare tool for R410A clutch type Conventional flare tool Clutch type Ridgid type Wing nut type Imperial type A 0 0 5 mm 1 0 1 5 mm 1 5 2 0 mm 5 Check that the flaring is properly made a b c...

Страница 16: ...tem cap is sealed where indicated with the arrow Do NOT damage it After handling the stop valve tighten the stem cap and check for refrigerant leaks Item Tightening torque N m Stem cap liquid side 13...

Страница 17: ...is might cause liquid compression or deterioration of oil return Oil traps in the rising gas piping can prevent this If Then The indoor unit is installed higher than the outdoor unit Install an oil tr...

Страница 18: ...be caused by e g the closed state of the expansion valve in the outdoor unit circuit but does NOT present any problem for correct operation of the unit 6 5 5 To perform vacuum drying 1 Vacuum the sys...

Страница 19: ...nents with specific functions e g valves The refrigerant circuit therefore features additional service ports for vacuuming pressure relief or pressurizing the circuit In case it is required to perform...

Страница 20: ...ize up G2 m Total length of 6 4 mm liquid piping 2 Determine R1 and R2 If Then G1 30 m a Use the table below to determine R1 length G1 30 m a and R2 length G2 If Then G1 30 m a and G1 G2 30 m a R1 0 0...

Страница 21: ...see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Greenhouse gas emissions of the total refrigerant charge expressed as tonnes CO2 equivalent f GWP Global warmin...

Страница 22: ...d conductor wire with round crimp style terminal c b b a c a B B a Terminal b Screw c Flat washer Tightening torques Item Tightening torque N m M4 X1M 1 2 1 8 M4 earth 1 2 1 4 M5 X1M 2 0 3 0 M5 earth...

Страница 23: ...ies a b a b a b 2 3 1 a Power supply cable b Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at th...

Страница 24: ...rate the unit without thermistors and or pressure sensors switches Burning of the compressor might result NOTICE Do NOT operate the unit until the refrigerant piping is complete when operated this way...

Страница 25: ...the unit to cooling operation mode 2 Start the test run Action Result 1 Go to the home menu Cool Set to 28 C 2 Press at least 4 seconds The Service Settings menu is displayed 3 Select Test Operation...

Страница 26: ...he user what to do in relation to maintaining the unit 9 Maintenance and service NOTICE Maintenance must be done by an authorised installer or service agent We recommend to do maintenance at least onc...

Страница 27: ...ANGER RISK OF EXPLOSION Pump down Refrigerant leakage If you want to pump down the system and there is a leakage in the refrigerant circuit Do NOT use the unit s automatic pump down function with whic...

Страница 28: ...A B C D E HB HU HD B 100 A B C 100 100 100 B E 100 1000 500 A B C E 150 150 150 1000 500 D 500 D E 1000 500 500 500 500 B D 100 100 B D E HB HD HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500...

Страница 29: ...red to install a roof but seal the gap between the upper and lower units to prevent discharged air from flowing back to the suction side through the bottom of the unit 12 2 Piping diagram Outdoor unit...

Страница 30: ...1U F2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG100 140_V1 RZQSG125 140_V1 F1U F4U Fuse F6U Fuse T 5 0 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQ S G_Y1 F1U F2U Fuse 31...

Страница 31: ...ed company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure...

Страница 32: ...4P385522 1A 2016 10 Copyright 2014 Daikin...

Отзывы: