ESIE15-13C
Field Setting from Remote Controller
Field Setting
79
Graph 2
Target evaporating temperature control when "low humidity application" is selected. Field
setting 16(26)-2-03:
Te target
(˚C)
Te target acceptable area
Remote controller setting temp.
Te target limited
≤
20˚C
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp.
>
setting
→
Te target down
Indoor temp.
<
setting
→
Te target up
Te target limited
≥
0˚C
Freeze protection
(40 min. integrated coil temp.
≤
-1˚C)
Indoor Temp
(˚C DB)